NOTE: A thermostatic expansion valve (TXV) is required on all 38BYB units. Step 4 refers to the installation of the TXV.
Step 4ÐRemove Indoor AccuRater® Piston and Install
TXV
For proper unit operation and reliability, units must be installed with a
After removing existing AccuRater from indoor coil, install
COIL
SENSING
BULB
EQUALIZER
TUBE
THERMOSTATIC
EXPANSION
VALVE
A88382
Fig. 7ÐTypical TXV Installation
10 O'CLOCK
2 O'CLOCK
SENSING BULB |
STRAP |
SUCTION TUBE |
8 O'CLOCK | 4 O'CLOCK |
7⁄8 IN. OD & SMALLER | LARGER THAN 7⁄8 IN. OD |
| A81032 |
Fig. 8ÐPositioning of Sensing Bulb
For TXV kit part number and charging instruction, refer to TXV label in your unit. If the indoor unit (fan coil) comes factory equipped with a
Install TXV kit to indoor coil as follows:
1.Install suction tube adapter.
2.Install liquid
3.Connect external equalizer tube to fitting on suction tube adapter.
4.Position sensing bulb on horizontal portion of suction tube adapter. Secure using supplied hardware.
5.Insulate bulb after installation. (See Fig. 8.)
6.Leak check all connections.