Carrier 38GXC, 40GXQ Outdoor Unit Installation, If piping is going through the right or left side

Models: 38GXC 38GXQ 40GXC 40GXQ

1 12
Download 12 pages 11.52 Kb
Page 7
Image 7
If piping is going through the right or left side:

If piping is going through the right or left side:

1.Use a small saw blade to carefully remove the correspond- ing plastic covering on side panel and drill the appropriate size hole where the pipe is going through the wall. See Fig. 8(c).

2.Remove knockout 1 if you are running only the wiring. Remove knockout 1 and 2 or knockout 1, 2 and 3 if you are running both piping and wiring through the side of the unit.

OUTDOOR UNIT INSTALLATION

1.Use a rigid base to support unit in a level position.

2.Locate outdoor unit and connect piping and wiring.

!CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Excessive torque can break flare nut depending on installation conditions.

Piping Connections to Outdoor Unit

IMPORTANT: Use refrigeration grade tubing ONLY. No other type of tubing may be used. Use of other types of tubing will void manufacturer’s warranty.

Make sure there is enough piping to cover the required length between the outdoor and indoor unit.

Piping Guide:

SDo not open service valves or remove protective caps from

tubing ends until all the connections are made.

SBend tubing with bending tools to avoid kinks and flat spots. S Keep the tubing free of dirt, sand, moisture, and other

contaminants to avoid damaging the refrigerant system.

S Avoid sags in the suction line to prevent the formation of oil traps. Insulate each tube with minimum 3/8-in. (10 mm) wall thermal pipe insulation. Inserting the tubing into the insulation before making the connections will save time and improve installation quality.

1.Remove service valve cover if provided with unit.

2.Cut tubing with tubing cutter.

3.Install correct size flare nut onto tubing and make flare con- nection.

4.Apply a small amount of refrigerant oil to the flare connec- tion on the tubing.

5.Properly align tubing in with service valve.

6.Tighten flare nut and finish installation using two wrenches as shown in Fig. 10.

A07354

Fig. 10 ---Tighten Flare Nut

INSTALL ALL POWER AND INTERCONNECTING WIRING TO OUTDOOR UNIT

Strong wind

 

A07350

 

 

Fig. 11 ---High Wind Installation

 

Outdoor Unit Wiring Connections

 

1.

Mount outdoor power disconnect.

 

2.

Run power wiring from main box to disconnect per NEC

38/40GXC(Q)

4.

Connect conduit to the conduit panel on sizes 9k, 12k, and

 

and local codes. Set outdoor unit in place.

 

3.

Remove field wiring cover (on sizes 9k, 12k, and 18k) from

 

 

unit by removing screws. On size 24k, use the knockout

 

 

provided on the end panel.

 

 

18k. (See Fig. 12)

 

5.

Properly connect both power supply and control lines to ter-

 

 

 

minal block per the connection diagram.

 

6.

Ground unit in accordance with NEC and local electrical

 

 

codes.

 

7.

Use lock nuts to secure conduit.

 

8.

Reinstall field wiring cover on 9k, 12k, and 18k units.

 

!CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

SBe sure to comply with local codes while running wire

from indoor unit to outdoor unit.

SEvery wire must be connected firmly. Loose wiring may cause terminal to overheat or result in unit malfunction.

A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.

SNo wire should be allowed to touch refrigerant tubing, compressor or any moving parts.

SDisconnecting means must be provided and shall be

located within sight and readily accessible from the air conditioner.

SConnecting cable with conduit shall be routed through hole in the conduit panel.

7

Page 7
Image 7
Carrier 38GXC, 40GXQ, 40GXC Outdoor Unit Installation, If piping is going through the right or left side, Piping Guide