Carrier 40GXQ, 38GXQ Troubleshooting, 38GXC/GXQ - 40GXC/GXQ 009-024Diagnostic Codes, 38/40GXCQ

Models: 38GXC 38GXQ 40GXC 40GXQ

1 12
Download 12 pages 11.52 Kb
Page 11
Image 11
TROUBLESHOOTING

TROUBLESHOOTING

This unit has onboard diagnostics. Error codes will appear on the LED display on the front panel of the indoor unit in place of the temperature display. Error codes are also displayed on the outdoor unit microprocessor board with colored LED lights. The table below explains the error codes for both units.

38GXC/GXQ - 40GXC/GXQ 009-024 Diagnostic Codes

 

 

LED Display on Outdoor Unit Board

 

 

Code Displayed

 

 

 

 

Equipment Fault

Green

Red

Yellow

Possible Cause

on Indoor Unit

LED

LED

LED

 

Front Panel

Number

Number

Number

 

 

 

of Flashes

of Flashes

of Flashes

 

 

 

 

 

 

 

Freeze Protection, Indoor Coil

E2

 

4

3

Low Refrigerant Charge, Blocked Indoor Air

 

Flow, or Dirty Air Filter

 

 

 

 

 

 

 

 

 

 

 

High Compressor Discharge Temperature

E4

 

 

7

Low Refrigerant Charge, Blocked Capillary,

 

 

or High Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

Low Voltage Protection

E5

 

 

5

Low Voltage

 

 

 

 

 

 

Communication Error

E6

0

 

 

Wiring Error, or Communication Failure

 

 

 

 

 

 

Indoor Air Temperature Thermistor

F1

 

 

 

Bad Connection, or Sensor Failure

 

 

 

 

 

 

Indoor Coil Temperature Thermistor

F2

 

 

 

Bad Connection, or Sensor Failure

 

 

 

 

 

 

Outdoor Air Temperature Thermistor

F3

 

6

 

Bad Connection, or Sensor Failure

 

 

 

 

 

 

Outdoor Coil Temperature Thermistor

F4

 

5

 

Bad Connection, or Sensor Failure

 

 

 

 

 

 

Compressor Discharge Line Thermistor

F5

 

7

 

Bad Connection, or Sensor Failure

 

 

 

 

 

 

Defrost

H1

 

 

2

Unit going through normal defrost cycle

 

 

 

 

 

 

Compressor Overload Protection

H3

 

 

8

Low Refrigerant Charge, Blocked Capillary,

 

 

or Compressor Motor Failure

 

 

 

 

 

 

 

 

 

 

 

Compressor Over Current Protection

H4

 

 

6

High Ambient Temperature, or Loss of

 

 

Condenser Airflow

 

 

 

 

 

 

 

 

 

 

 

IPM Module Protection

H5

 

 

4

Loss of Cooling to Heat Sink, High Ambient,

 

 

Low Voltage, or Bad Connections

 

 

 

 

 

 

 

 

 

 

 

38/40GXC(Q)

11

Page 11
Image 11
Carrier 40GXQ, 38GXQ installation instructions Troubleshooting, 38GXC/GXQ - 40GXC/GXQ 009-024Diagnostic Codes, 38/40GXCQ