Carrier 48/50P5030-100, 48/50P4, 48/50P2 Installation, Install Field-FabricatedWind Baffles

Models: 48/50P5030-100 48/50P3 48/50P2 48/50P4

1 16
Download 16 pages 36.84 Kb
Page 3
Image 3
Table 4 — Motormaster V Control Package Usage

Table 3 — Motormaster V Control Package Contents — 48/50P070-100 Units

ITEM

CRLOWAMB036A00

CRLOWAMB037A00

CRLOWAMB038A00

Connector (1/2-in.)

 

HW60EA001 (2)

 

Connector (1-in.)

 

HW60HH006 (2)

 

Controller, 230 V 2 Hp

HR46TN001 (2)

Controller, 460 V 2 Hp

HR46TN002 (2)

Controller, 575 V 2 Hp

HR46TN003 (2)

Enclosure

 

30RA500381 (2)

 

Enclosure Cover

 

30RA500519 (2)

 

Enclosure Mounting Bracket

 

50EJ500656 (2)

 

Fan Relay

 

HN61KK055 (2)

 

Relay Base

 

HN79KK035 (2)

 

Fuse Block

 

HY11UT035 (2)

 

Fuse 15A, KTK-R, Class CC

HY10KB151 (6)

HY10KB151 (6)

Fuse 20A, KTK-R, Class CC

HY10KB200 (6)

Harness Assembly

 

48ZZ401971 (2)

 

Harness Assembly

 

48EJ402454 (2)

 

Harness Assembly

 

48ZZ402001 (2)

 

Label

 

48ZZ502002

 

Transducer

 

HK05ZZ001 (2)

 

Transducer Harness

 

48EJ403240 (2)

 

Varnish Cloth (Large)

 

48DA510141 (2)

 

Varnish Cloth (Small)

 

38C24601 (2)

 

Wire Tie

 

HY76TB123 (6)

 

Wire Tie

 

HY76TB045 (2)

 

Wire, 16 Gage 72 in. Long

 

WHT (2), GRY (2)

 

Table 4 — Motormaster V Control Package Usage

UNIT

VOLTAGE

ITEM DESCRIPTION

 

208/230

CRLOWAMB033A00

48/50P030-060

 

 

380, 400, 460

CRLOWAMB034A00

 

 

 

 

575

CRLOWAMB035A00

 

 

 

 

208/230

CRLOWAMB036A00

48/50P070-100

 

 

380, 400, 460

CRLOWAMB037A00

 

 

 

 

575

CRLOWAMB038A00

 

 

 

INSTALLATION

Pre-InstallationInspect the contents of this accessory package before installing. File a claim with the shipper if there is shipping damage or if a part is missing.

Step 1 — Install Field-Fabricated Wind Baffles

INSTALLATION WARNING

To avoid the possibility of electrical shock, open all discon- nects before installing or servicing this accessory.

On size 040-060 units, in areas with prevailing winds of more than 5 mph (8 kph) and where temperatures drop below 32 F (0° C), wind baffles must be field fabricated to ensure

proper cooling cycle operation at low-ambient temperatures with Motormaster V controls. Wind baffles are not needed on size 030, 035, and 070-100 units. See Fig. 2 for baffle details. Use 20-gage (1 mm) galvanized sheet metal, or similar corro- sion-resistant material for the baffles. Use field-supplied screws to attach baffles to unit. Screws should be 1/4-in. (6.3 mm) diam- eter or larger. Screws should not be more than 1/2-inch in length. Drill required screw holes for mounting baffles.

Step 1 — Install Field-Fabricated Wind Baffles CAUTION

To avoid damage to refrigerant coils, electrical compo- nents, and wiring use extreme care when drilling screw holes and screwing in fasteners.

3

Page 3
Image 3
Carrier 48/50P5030-100, 48/50P4 Installation, Install Field-FabricatedWind Baffles, Motormaster V Control Package Usage