Step 2 — Mounting and Electrical Connec- tions for Motormaster® V Control

WARNING

To avoid possibility of electric shock and personal injury, open and tag all electrical disconnects before installing or servicing unit.

WARNING

Hazard of electric shock. Wait three minutes after discon- necting incoming power before servicing drive. Capacitors retain charge after power is removed.

CAUTION

To avoid damage to the small terminals on the Motormas- ter V control, use care when tightening the compression terminals and use the proper size screwdriver.

CAUTION

DO NOT connect incoming AC power to Motormaster V output terminals T1, T2, and T3. Severe damage to the con- trol will result.

48/50P030-060 UNITS — For 48/50P030-035 units, the Mo- tormaster controlled outdoor-fan motor (OFM) is the no. 1 OFM (see Fig. 3). The no. 2 OFM is controlled by the Com- fortlink head pressure control routine.

For 48/50P040 units, the Motormaster controlled outdoor- fan motor (OFM) is the no. 3 OFM (see Fig. 3). The no. 1 and 2 OFMs are controlled by the Comfortlink head pressure control routine.

For 48/50P050-060 units, the Motormaster controlled out- door-fan motor (OFM) is the no. 1 OFM (see Fig. 3). The no. 2, 3, and 4 OFMs are controlled by the Comfortlink head pressure control routine.

Use the following procedure to mount and connect the MMV controllers to these units:

1.Disconnect power to the unit. Lockout and tag power dis- connect.

2.Remove control box covers.

3.For size 030-035 units, remove panel from condenser section on OFM 1 side of the unit in order to gain access to the outdoor fan section. See Fig. 4. For size 040-060 units, remove panel above control box as shown in Fig. 5 and 6.

4.Mount accessory fuse block HY11UT035 and fan relay base HN79KK035 inside control box as shown in Fig. 7. Secure components with ½-in. sheet metal screws.

a.Insert fuses into fuse blocks and relays into relay bases.

b.Install harness 48EJ402454 from load side of CCB (control circuit breaker terminals 21, 22, 23) to line side of MMF (Motormaster V fuse block) as shown in Fig. 8. Note that it may be easier to pick up the load side of CCB from the ¼-in. male quick connect terminals on the line side (terminals 11, 12, 13) of the OFC contactors (see power sche- matic on control box door).

c.Connect FR (fan relay) coil to OFC1 coil using the 72-in. long 16 gage white and gray wires (stripped end goes to FR) as shown in Fig. 8.

5.Mount the MMV controller enclosure 30RA500381 on the bulkhead of the unit inside the outdoor fan section, as shown in Fig. 4-6, using the mounting brackets 50EJ500656 installed on the enclosure. Remove the en- closure cover and install the ½-in. HW60EA001 and 1-in. HW60HH006 connectors in the holes in the lower right hand side of the enclosure.

6.Connect transducer HK05ZZ001 to the liquid line service Schrader port of refrigerant Circuit A. Plug transducer ca- ble 48EJ403240 into transducer. Run cable to the MMV enclosure, as shown in Fig. 4-6.

Run MMPT (Motormaster V pressure transducer) cable through ½-in. connector of MMV enclosure (do not tight- en connector screws at this time). Connect red, green, and black wires to MMV terminals 6, 5, and 2 as shown in Fig. 8. Terminate drain wire of transducer cables under one of the lower MMV mounting screws.

7.Make remaining electrical connections to MMV (see Fig. 8).

a.In main control box, disconnect black, red, blue, and green wires from load side (terminals 21, 22, 23) of OFC1 (sizes 030-035, 050-060) contactor or OFC 3 (size 040) (label cable from OFC1 or OFC3 (size 040) as OFM1 or OFM3 (size 040). Pull wires out through the hole in the bottom of the control box and run them up the corner post to the opening of the cable tray on the side of the control box, as shown in Fig. 4-6. Run the cable through the wire tray to the MMV enclosures.

b.Run the OFM1/OFC3 (040) cable through the 1-in. connector of the MMV enclosure (do not tighten connector screws at this time). Remove ring termi- nals from black, red, and blue wires and strip insu- lation back 3/8-in. Connect black, red, and blue wires to MMV terminals T1, T2, and T3. Connect green ground wire to MMV ground screw.

c.In the main control box connect Motormaster VFD (variable frequency drive) harness 48ZZ401971 to the load side of the MMF (label the opposite end of this harness as MMF). Run the harness along the bottom of the control box and out through the hole that the OFM harness was in. Pull the harness out through the hole in the bottom of the control box and run it through the opening of the cable tray (in the same manner as the OFM harnesses).

d.Run the MMF cable through 1-in. connector of the MMV enclosure (do not tighten connector screws at this time). Connect L1, L2, and L3 wires to MMV terminals L1, L2, and L3. Connect green ground wire to MMV ground screw. Place 1 large varnish cloth 48DA510141 around both cables at the point they enter the 1-in. connector. Tighten down connector screws being careful not to dam- age the cables.

e.In the main control box connect one Motormaster VFD harness 48ZZ402001 to the NO (normally open) contact of the FR (see Fig. 8). Run the har- nesses along the bottom of the control box and out through the hole that the OFM harness was in. Pull the harness out through the hole in the bottom of the control box and run it through the opening of the cable (in the same manner as the OFM harness).

5

Page 5
Image 5
Carrier 48/50P2, 48/50P4, 48/50P3, 48/50P5030-100 installation instructions

48/50P5030-100, 48/50P3, 48/50P2, 48/50P4 specifications

The Carrier 48/50P5030-100, 48/50P4, 48/50P3, and 48/50P2 series represent a range of highly efficient air conditioning and heating solutions developed by Carrier. Designed for commercial and industrial applications, these units combine advanced technology with robust features to deliver reliable performance and comfort.

One of the standout features of the Carrier 48/50P series is their energy efficiency. These units are equipped with high-efficiency compressors and fans that optimize energy use while maintaining superior cooling and heating capabilities. The models often meet or exceed ASHRAE efficiency standards, providing significant energy savings over traditional systems. This makes them not only cost-effective over their lifespan but also a responsible choice for energy-conscious businesses.

The 48/50P5030-100 model is notable for its ability to deliver precise temperature control, thanks to its sophisticated microprocessor control panel. This control system allows for easy adjustments and provides valuable diagnostic information, ensuring operational reliability and maintenance efficiency. The advanced controls also support variable-speed technology, which adjusts the system’s output based on real-time demands, enhancing both comfort and energy savings.

In terms of construction, these units are designed for durability. With a rugged, weather-resistant cabinet and high-quality components, they can withstand harsh environmental conditions, making them suitable for a variety of settings. The units typically include high-efficiency filters that improve indoor air quality by reducing airborne particles and allergens.

Another key characteristic of the Carrier 48/50P series is their versatility. These units can be configured for various applications, including rooftop installations and ground-mounted setups. Their modular design allows for easy integration into existing systems, accommodating different space requirements while providing optimal performance.

Carrier also emphasizes noise reduction in the design of these units, incorporating sound-dampening technologies that minimize operational noise. This is particularly valuable in environments where quiet operation is essential, such as schools and offices.

Overall, the Carrier 48/50P5030-100, 48/50P4, 48/50P3, and 48/50P2 series represent a commitment to quality, efficiency, and innovation in climate control solutions. With their advanced features, energy-saving technologies, and robust design, these models are well-suited to meet the diverse needs of modern commercial and industrial facilities. Carrier continues to lead the industry by integrating cutting-edge technology with a focus on performance and sustainability, ensuring that their systems provide long-term comfort and efficiency.