CERTIFIED DIMENSION PRINT

REQ'D CLEARANCES FOR SERVICING Ð in. (mm)

Duct Panel

. . . . .

0. . .

Unit Top

. . . 36

(914.4)

Side Opposite Ducts

. . . 36

(914.4)

Compressor Access

. . . 36

(914.4)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L

 

 

Ð in. (mm)

 

 

 

 

Maximum Extension of Overhangs . . .

. . . 48 (1219.2)

Unit Top

. . . 14

(355.6)

Duct Side of Unit

2 (50.8)

Side Opposite Ducts

. . . 14

(355.6)

Bottom of Unit

. . . . .

0. . .

Flue Panel

. . . 36

(914.4)

NEC (National Electrical Code) REQ'D CLEARANCES

 

 

 

 

Ð in. (mm)

 

 

 

 

 

 

Between Units, Control Box Side . . . .

. . . 42 (1066.8)

Unit and Ungrounded Surfaces,

 

 

 

Control Box Side

. . . 36

(914.4)

Unit and Block or Concrete Walls and Other

 

 

Grounded Surfaces, Control Box Side

. . . 42 (1066.8)

NOTE: Clearances must be maintained to prevent recircu- lation of air from outdoor fan discharge.

OUTDOOR COIL

UNIT

 

ELECTRICAL

UNIT

CORNER WEIGHT

 

 

WEIGHT

 

(lb/kg)

 

48SS

CHARACTERISTICS

lb

kg

A

B

C

D

 

 

 

048080

 

208/230-1-60

414

188

107/49

83/38

158/72

66/30

048100/120/140

 

208/230-1-60

426

193

110/50

86/39

159/72

71/32

060080

 

208/230-1-60

453

206

117/53

93/42

167/76

76/35

INDOOR COIL

 

208/230-1-60

465

211 120/55 96/44 167/76 82/37

060100/120/140

 

UNIT

 

 

CENTER OF GRAVITY

 

 

 

 

 

 

(in./mm)

 

 

 

48SS

 

X

 

 

Y

 

Z

 

 

 

 

 

 

 

048080

 

28.76/731

 

23.46/596

 

15.35/390

048100/120/140

28.42/722

 

23.42/595

 

15.35/390

060080

 

28.36/720

 

23.27/591

 

15.35/390

060100/120/140

27.95/710

 

23.23/590

 

15.35/390

INDOOR COIL ACCESS

5

Page 5
Image 5