29
The raceway providesthe UL required clearance between
high-- and low--voltage wiring. Pass the control wires
through the hole provided in the corner post, then feed the
wires thorough the raceway to the RTU--MP. Connect to
the wires to the removable Phoenix connectors and then
reconnect the connectors to the board.
Space Temperature (SPT) Sensors
A field--supplied Carrier space temperature sensor is
required with the RTU--MP to monitor space temperature.
There are 3 sensorsavailable for this application:
S33ZCT55SPT,space tempe rature sensor with override
button
S33ZCT56SPT,space tempe rature sensor with override
button and setpoint adjustment
S33ZCT59SPT,space temperature sensor withLCD
(liquid crystal display) screen, override button, and
setpoint adjustment
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three--conductorshielded cable forthe sensor and setpoint
adjustment connections. If the setpoint adjustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two--conductor,twisted pair cable may be used.
Connect T--55 -- See Fig. 31 for typical T --55 internal
connections. Connect the T--55 SEN terminals to
RTU--MP J20--1and J20 --2. See Fig. 50.
SEN
SEN
J20-1
J20-2
C08460
Fig. 50 --RTU--MP T--55Sensor Connections
Connect T--56 -- See Fig. 33 for T --56 internal
connections. Install a jumper between SEN and SET
terminals as illustrated. Connect T--56 terminals to
RTU--MP J20--1, J20--2 and J20--3 per Fig. 51.
SEN J20-1
J20-2
SEN
SET
Jumper
J20-3
SET
C08461
Fig. 51 --RTU--MP T--56Sensor Connections
Connect T--59 -- The T--59 space sensor requires a
separate, isolated power supply of 24 VAC. See Fig. 51
for internal connections at the T--59. Connect the SEN
terminal (BLU) to RTU--MP J20--1. Connect the COM
terminal (BRN)to J20--2. Connectthe SET terminal (STO
or BLK) to J20--3.
OR SET SEN
OPB COM- PW R+
BLU (SPT)
BLK (STO)
24 VAC
SENSOR
WIRING
POWER
WIRING
BRN (COM)
NOTE: Mustuse a separate isolated transformer.
C07132
Fig. 52 --Space Temperature Sensor Typical Wiri ng
(33ZCT59SPT)
Economizercontrols —
Outdoor Air Enthalpy Control (PNO HH57AC077) --
The enthalpy control (HH57AC077) is available as a
field--installedaccessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field--installed
accessory return air enthalpy sensor (HH57AC078) is
required for differential enthalpy control. See “Return Air
Enthalpy Sensor”below.)
Locate the enthalpy control in the economizer hood.
Locate two GRA leads in the factory harnessand connect
these leads to enthalpy control sensors 2 and 3. See
Fig. 36. Connect the enthalpy control power input
terminals to economizer actuator power leads RED
(connect to TR) and BLK (connect to TR1).
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Differential Enthalpy Control — Differential enthalpy
control is provided by sensing and comparing the outside
air and return air enthalpy conditions. Install t he outdoor
air enthalpy control as described above. Add and installa
return air enthalpy sensor.
Return Air Enthalpy Sensor — Mount the return--air
enthalpy sensor (HH57AC078) in the return--airduct. The
return air sensor is wired to the enthalpy controller
(HH57AC077). See Fig. 37.
To wire the return air enthalpy sensor, perform the
following:
1. Use a 2--conductor,18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the enthal-
py controller.
2. At the enthalpy control remove the factory--installed
resistor from the (SR) and (+) terminals.
3. Connect the field--supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(SR+) terminal on the enthalpy controller. Connect
the BLK wire to (S) spade connector on the return air
50TCQA