Table 8—Cooling Charging Chart
SUCTION LINE TEMPERATURE (°F)
Suction Line Pressure (PSIG)
OD Temp. (°F) | 52 | 54 | 56 | 59 | 61 | 64 | 67 | 70 | 73 | 76 | 79 | 82 | 85 | 89 | 92 |
45 | 51 | 55 | 60 | 64 | 69 | — | — | — | — | — | — | — | — | — | — |
55 | — | — | 53 | 57 | 62 | 66 | 70 | — | — | — | — | — | — | — | — |
65 | — | — | — | — | 53 | 57 | 62 | 66 | 71 | 75 | — | — | — | — | — |
75 | — | — | — | — | — | — | — | 56 | 61 | 66 | 71 | 76 | — | — | — |
85 | — | — | — | — | — | — | — | — | 53 | 58 | 63 | 67 | 72 | — | — |
95 | — | — | — | — | — | — | — | — | — | 50 | 54 | 58 | 62 | 66 | — |
105 | — | — | — | — | — | — | — | — | — | — | 50 | 53 | 57 | 60 | 64 |
115 | — | — | — | — | — | — | — | — | — | — | 49 | 52 | 55 | 58 | 61 |
125 | — | — | — | — | — | — | — | — | — | — | — | 50 | 53 | 56 | 59 |
SUCTION LINE TEMPERATURE (°C)
Suction Line Pressure (kPa)
OD Temp. (°C) | 361 | 370 | 387 | 405 | 423 | 442 | 462 | 482 | 502 | 523 | 544 | 566 | 589 | 612 | 636 |
7 | 11 | 13 | 15 | 18 | 21 | — | — | — | — | — | — | — | — | — | — |
13 | — | — | 12 | 14 | 16 | 19 | 21 | — | — | — | — | — | — | — | — |
18 | — | — | — | — | 12 | 14 | 17 | 19 | 21 | 24 | — | — | — | — | — |
24 | — | — | — | — | — | — | — | 13 | 16 | 19 | 22 | 24 | — | — | — |
29 | — | — | — | — | — | — | — | — | 12 | 14 | 17 | 20 | 22 | — | — |
35 | — | — | — | — | — | — | — | — | — | 10 | 12 | 14 | 17 | 19 | — |
41 | — | — | — | — | — | — | — | — | — | — | 10 | 12 | 14 | 16 | 18 |
46 | — | — | — | — | — | — | — | — | — | — | 9 | 11 | 13 | 14 | 16 |
52 | — | — | — | — | — | — | — | — | — | — | — | 10 | 11 | 13 | 15 |
COOLING OPERATION (SIZES
With a call for cooling (Y/Y2), the indoor fan energizes immedi- ately whereas the contactor energizes after a 5 minute time delay (in case of initial
COOLING OPERATION (SIZES 048 AND 060)
These units utilize a 2 stage indoor thermostat. With a first stage call for cooling (Y1), the indoor fan (low stage) energizes immediately whereas the contactor energizes after a 5 minute time delay (in case of an initial
HEATING OPERATION (SIZES
With a call for heating (Y1), the indoor fan (low stage) energizes immediately whereas the contactor energizes after a 5 minute time delay (in case of initial
HEATING OPERATION (SIZES 048 AND 060)
With a first stage call for heating (Y1), the indoor fan (low stage) energizes immediately whereas the contactor energizes after a 5 minute time delay (in case of initial
heating (Y2) energizes switching the compressor into high stage heating through energizing an internal solenoid valve inside the scroll compressor and switching the indoor fan into high stage. The auxiliary or backup heat is controlled by a third stage (W2). If the demand is not met, W3 is energized in case of staged heating. When heating demand is satisfied, W3, W2 and Y2 sequentially
CONTINUOUS FAN
With the continuous Indoor fan option selected on the thermostat, G is continuously energized. In case of
DEFROST
Defrost board (DB) is a time and temperature control, which includes a
Defrost mode is identical to Cooling mode. The outdoor fan motor stops because of “OF1” and “OF2” contacts opening on the defrost board, a bank of optional electric heat turns on to warm air supplying the conditioned space.
ELECTRIC RESISTANCE HEATING
If accessory electric heaters are installed, on a call for “Emergency Heat” the thermostat energizes W which energizes the heater relay and in turn energizes the electric heaters. The IFR is energized which starts the
MAINTENANCE
To ensure continuing high performance, and to reduce the possi- bility of premature equipment failure, periodic maintenance must
14