A05209
Fig. 11C—Accessory Electric Heater Wiring
Table 6—Electrical Data—50ZHA
|
|
| VOLTAGE | COMPRESSOR |
|
| ELECTRIC HEAT | SINGLE POINT POWER SUPPLY | ||||||
UNIT SIZE |
| RANGE | OFM | IFM | ||||||||||
|
|
|
|
|
|
|
| |||||||
50ZHA | MIN |
| MAX | RLA | LRA | FLA | FLA | Nominal KW* | FLA | MCA | FUSE OR | MOCP | ||
|
| |||||||||||||
|
|
|
|
|
| CKT BKR | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 18.6/18.6 | 25/25 | — | ||
| 024 | 187 |
| 253 | 10.9 | 54.0 | 0.9 | 4.1 | 3.8/5.0 | 18.1/20.8 | 41.2/44.7 | 45/50 | — | |
|
| 7.5/10.0 | 36.1/41.7 | 63.8/70.7 | — | 60/70 | ||||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| 5.4/7.2 | 26.0/30.0 | 51.1/56.1 | 50/50 | — |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 21.8/21.8 | 30/30 | — | ||
| 030 |
|
|
|
|
|
|
|
| 3.8/5.0 | 18.1/20.8 | 44.4/47.9 | 50/50 | — |
| 187 |
| 253 | 13.5 | 72.5 | 0.9 | 4.1 | 7.5/10.0 | 36.1/41.7 | 57.0/73.9 | — | 70/70 | ||
|
|
|
|
|
|
|
|
|
| 11.3/15.0 | 54.2/62.5 | 89.5/100.0 | — | 90/100 |
|
|
|
|
|
|
|
|
|
| 5.4/7.2 | 26.0/30.0 | 54.3/59.3 | 60/60 | — |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 29.4/29.4 | 35/35 | — | ||
| 036 |
|
|
|
|
|
|
|
| 3.8/5.0 | 18.1/20.8 | 52.0/55.4 | 60/60 | — |
| 187 |
| 253 | 17.5 | 88.0 | 1.5 | 6.0 | 7.5/10.0 | 36.1/41.7 | 74.5/81.5 | — | 80/80 | ||
|
|
|
|
|
|
|
|
|
| 11.3/15.0 | 54.2/62.5 | 97.1/107.5 | — | 100/100 |
|
|
|
|
|
|
|
|
|
| 5.4/7.2 | 26.0/30.0 | 61.9/66.9 | — | 70/70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 31.7/31.7 | 40/40 | — | ||
|
|
|
|
|
|
|
|
|
| 3.8/5.0 | 18.1/20.8 | 54.3/57.8 | — | 60/70 |
| 042 | 187 |
| 253 | 19.4 | 104.0 | 1.5 | 6.0 | 7.5/10.0 | 36.1/41.7 | 76.9/83.8 | — | 80/90 | |
|
| 11.3/15.0 | 54.2/62.5 | 99.4/109.9 | — | 100/110 | ||||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| 15.0/20.0 | 72.2/83.3 | 122.0/135.9 | — | 110/150 |
|
|
|
|
|
|
|
|
|
| 5.4/7.2 | 26.0/30.0 | 63.2/69.2 | — | 70/80 |
|
|
|
|
|
|
|
|
|
| 40.0/40.0 | 50/50 | — | ||
|
|
|
|
|
|
|
|
|
| 3.8/5.0 | 18.1/20.8 | 62.6/66.1 | — | 80/80 |
| 048 | 187 |
| 253 | 24.7 | 116.0 | 1.5 | 7.7 | 7.5/10.0 | 36.1/41.7 | 85.1/92.1 | — | 100/100 | |
|
| 11.3/15.0 | 54.2/62.5 | 107.7/118.1 | — | 110/125 | ||||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| 15.0/20.0 | 72.2/83.3 | 130.3/144.2 | — | 125/125 |
|
|
|
|
|
|
|
|
|
| 5.4/7.2 | 26.0/30.0 | 72.5/77.5 | — | 90/90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| — | 45.7/45.7 | 60/60 | — | |
|
|
|
|
|
|
|
|
|
| 3.8/5.0 | 18.1/20.8 | 68.2/71.7 | — | 90/90 |
| 060 | 187 |
| 253 | 28.0 | 118.0 | 3.0 | 7.7 | 7.5/10.0 | 36.1/41.7 | 90.8/97.8 | — | 100/110 | |
|
| 11.3/15.0 | 54.2/62.5 | 113.4/123.8 | — | 125/125 | ||||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| 15.0/20.0 | 72.2/83.3 | 135.9/149.9 | — | 125/150 |
|
|
|
|
|
|
|
|
|
| 5.4/7.2 | 26.0/30.0 | 78.2/83.2 | — | 90/100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLA | Full Load Amps |
|
|
|
|
|
|
|
|
|
|
|
| |
LRA | Locked Rotor Amps |
|
|
|
|
|
|
|
|
|
|
|
| |
MCA | Minimum Circuit Amps |
|
|
|
|
|
|
|
|
|
|
|
| |
MOCP Maximum Overcurrent Protection |
|
|
|
|
|
|
|
|
|
| ||||
RLA | Rated Load Amps |
|
|
|
|
|
|
|
|
|
|
|
|
NOTES:
1.In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be Power Supply fuse. The CGA (Canadian Gas Association) units may be fuse or circuit breaker.
2.Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC.
12