WIRING ENTRY HOLE | ENTRY HOLE |
A05198
Fig. 7—Unit Electrical Connection
C00011
Fig. 8—Control Box Wiring
START-UP
Use the
Step 1—Check for Refrigerant Leaks
LOCATE AND REPAIR REFRIGERANT LEAKS AND CHARGE THE UNIT AS FOLLOWS:
1.Using both high- and
2.Repair leak following accepted practices.
Step
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage.
Complete the required procedures given in the
Do not operate the compressor in cooling mode when the outdoor temperature is below 40 F.
Do not
CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as follows:
1.Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down within 60 seconds (for
2.Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room temperature. Observe that compressor, outdoor fan, and indoor blower motors start and that reversing valve shifts. Observe that cooling cycle shuts down when control setting is satisfied. Reversing valve (RV) remains energized.
3.Place system switch in HEAT position. Observe that compres- sor, indoor fan and outdoor fan energize (Reversing Valve is deenergized in heat pump heating mode). Set control above room temperature. Observe that heating cycle shuts down when control setting is satisfied.
4.When using an automatic changeover room thermostat, place both SYSTEM and FAN switches in AUTO. positions. Observe that unit operates in Cooling mode when temperature control is set to ‘‘call for cooling’’ (below room temperature), and unit operates in Heating mode when temperature control is set to “call for heating” (above room temperature).
Step 3—Refrigerant Charge
Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate and in Table 2. Refer to Carrier Refrigerant Service Techniques Manual, Refrigerants section. Unit panels must be in place when unit is operating during charging procedure. Unit must operate a minimum of 15 minutes before checking charge.
NO CHARGE
Refer to Carrier Refrigerant Service Techniques. Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Table 2).
|
|
| UNIT GROUND | |
|
|
| GROUND | |
|
|
| LEAD | |
| L | BLK | ||
CONNECTIONS | ||||
|
| |||
CONNECTIONS | TO DISCONNECT | L | YEL | |
TO DISCONNECT | PER NEC | |||
PER NEC |
| L | BLU | |
|
|
NOTE: Install a
Fig. 9—Line Power Connections
C00012
8