Replace
board.
Turn on
power to unit.
Is blower running?
NO
Jumper across screws R & G.
Is
blower running
on cooling
speed?
YES
Is
NO115VAC across
& COM?
|
|
|
| START |
| ||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Disconnect all thermostat | |||
|
|
|
| wires from board. |
| ||
|
|
|
|
|
|
|
|
YES | Is 24VAC | YES | |||||
|
|
|
| across screws |
|
| |
|
|
|
|
|
|
R & C?
NO
Check/Replace:
1.Limit switch
2.Limit shield (if used)
3.Fuse link
4.Auxillary limit switch (if used)
5.Wire harness
Is
NO115VACNO across HI &
COM?
YES
Replace
blower motor
and/or start
capacitor.
Is 24VAC | YES |
| |
across screws |
| ||
|
| ||
W & C or |
|
| |
G & C? |
|
| |
| NO |
|
|
|
|
| |
|
|
|
|
Is
115VACYES across L1 &
L2?
NO
Check/Replace:
1.Unit power
2.Door switch
3.Power harness
Turn off
power to unit.
NO
Are
all thermostat wires to board disconnected?
YES
Replace
board.
YES
Is
24VAC
across screws
R & C?
NO
Check/Replace:
1.
2.Transformer
YES
Remove
R & G jumper.
Check pressure tube for leak or crimp; otherwise, replace pressure switch
YES
Is
24VAC
across
NO
NO | Replace | ||
|
|
| board. |
|
|
|
|
NODoes blower turn
off?
YES
Is heat
exchangerYES pressure drop greater
than
wc?
NO
YES
Is 24VAC
across pressure
switch N/O contact
&screw C on board?
NO
Repair wire
harness.
Jumper across screws R & W.
Is
inducer motor
on?
NO
Check/Replace:
1.Vent systems
2.Induce wheel
3.Flue choke
4.Inducer voltage
5.Inducer motor bearings
YES | Is | NO |
| unit lit? |
|
YES
Is 24VAC
across pressure
switch N/O contact
&screw C on board?
NO
Is
24VAC across gas
valve?
YES | Check/Replace: | ||||
|
|
| 1. | Draft safeguard switch | |
|
|
| |||
|
|
| 2. | Wire harness | |
|
|
|
| ||
|
|
|
| ||
YES | Check/Replace: | ||||
1. | Pilot | ||||
|
|
| |||
|
|
| 2. | Thermocouple | |
|
|
| 3. | Gas valve | |
|
|
|
|
|
Replace
YES
Is
115VAC across
Is
blower running NO on heat speed 45
Is
115VAC across
YES | Replace | |
blower motor | ||
|
inducer motor.
NO
Check/Repair wire harness; otherwise, replace pressure switch.
inducer motor
connector?
NO
Is
24VAC across
YES
Replace
board.
NO
sec after unit
lights?
YES
Is
115VAC
across
& COM?
YES
Remove
R & M jumper.
inducer motor
connector?
NO
Is
24VAC across
NO
Repair wire
harness.
|
|
|
| and/or start | ||
|
|
|
| capacitor. | ||
YES |
|
|
|
| ||
| Replace |
| ||||
|
|
|
|
| ||
|
|
|
| board. |
| |
|
|
|
|
| ||
|
|
|
| Check/Replace |
|
|
|
|
|
| thermostat |
| |
|
|
|
| and/or |
| |
|
|
| thermostat wiring. |
| ||
|
|
|
|
|
|
|
NO
After
turn off?
|
|
| NO |
|
|
|
|
Reconnect all |
| Does unit | |
thermostat wires. |
| operate? |
NOTE: After replacing any component, verify correct operating sequence as indicated by bold arrows.
YES |
END OF TEST. |
A91253