Carrier 58HDX Burner Box Assembly, Fire, Explosion, Unit Damage Hazard, Fire Or Explosion Hazard

Models: 58HDX

1 22
Download 22 pages 38.73 Kb
Page 5
Image 5
Fig. 4 - Burner Box Assembly

CELL PANEL FIRE, EXPLOSION, UNIT DAMAGE HAZARD

BURNERS

BURNER BOX

FIRE OR EXPLOSION HAZARD MANIFOLD

Manual background GAS VALVE

A07826

Fig. 4 - Burner Box Assembly

4.Remove wires from gas valve. Note location for reassembly.

5.Unplug igniter from harness.

6.Remove screws that secure manifold to burner box. (See Fig. 4.)

NOTE: Do not remove burner box from cell panel.

7.Remove manifold, orifices, and gas valve as 1 assembly.

8.Remove screws attaching burner assembly in burner box.

NOTE: Use care when removing and reinstalling burners not to strike the hot surface igniter.

9. Remove burner assembly from burner box.

NOTE: All burners are attached to burner bracket and can be removed as 1 assembly.

10.Clean burners with soft brush and vacuum.

11.Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure burners fit over orifices.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Igniter wires must be securely placed in slot in manifold grommet or else they could become pinched or severed and electrically shorted.

12.Reconnect wires to gas valve and igniter. Refer to furnace wiring diagram for proper wire location.

13.Reinstall gas supply pipe to furnace gas control valve using backup wrench on gas valve to prevent rotation and improper orientation.

NOTE: Use propane gas resistant pipe dope to prevent gas leaks. DO NOT use Teflon tape.

!WARNING

FIRE, EXPLOSION, UNIT DAMAGE HAZARD

Failure to follow this warning could result in property damage, personal injury, or death.

Gas valve switch MUST be facing forward or tilted upward.

14.

Turn on gas and electrical supplies to furnace.

 

 

 

 

 

 

 

 

!

WARNING

 

 

 

 

 

FIRE OR EXPLOSION HAZARD

 

 

Failure to follow the safety warnings could result in personal

 

 

injury, death, or property damage.

 

 

Never test for gas leaks with an open flame. Use a

 

58HDX

commercially available soap solution made specifically for the

 

detection of leaks to check all connections.

 

 

 

 

 

 

 

15.

Check for gas leaks.

 

 

16.

Replace main furnace door.

 

 

 

 

 

 

 

PRIMARY HX

INLET OPENINGS

A07827

Fig. 5 - Cleaning Inlet Openings of Primary Heat Exchangers

5

Page 5
Image 5
Carrier 58HDX Burner Box Assembly, Fire, Explosion, Unit Damage Hazard, Fire Or Explosion Hazard, Electrical Shock Hazard