Service and Maintenance Instructions

58MXA 4-Way Multipoise Fixed-Capacity Direct-Vent Condensing Gas Furnace

Visit www.carrier.com

Service and Maintenance Instructions

For Sizes 040Ð140, Series 130

A93040

NOTE: Read the entire instruction manual before performing any service or maintenance.

This symbol indicates a change since the last issue.

Index

Page

SAFETY CONSIDERATIONS

1-2

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS

2

GENERAL

2

CARE AND MAINTENANCE

2-11

Cleaning and/or Replacing Air Filter

3

Blower Motor and Wheel Maintenance

3-4

Cleaning Burners

4-5

Cleaning Heat Exchangers

5-7

Primary Heat Exchangers

5-7

Secondary Heat Exchangers

7

®

→For Sizes 040Ð140, Series 130SAFETY CONSIDERATIONSama

CANADIAN GAS ASSOCIATION

A P P R O V E D

R

As an ENERGY STAR® Partner, Carrier Corporation has determined that this prod- uct meets the ENERGY STAR® guidelines for energy efficiency.

 

 

 

 

 

 

 

®

 

 

• •

• • •

 

 

• • • • •

• •

U

L T

R

A

H I

G H E F

F I C I

E N C Y

 

G A

S

F

U R N A N C

E

 

A93007

Flushing Collector Box and Drainage System

7

Servicing Hot Surface Ignitor

7-8

Electrical Controls and Wiring

8

Troubleshooting

8-9-10

Checking Heat Tape Operation (If Applicable)

10

Winterizing

10-11

WIRING DIAGRAM

12

SERVICE LABEL

13

TROUBLESHOOTING GUIDE

14-15

SAFETY CONSIDERATIONS

Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person- nel should install, repair, or service heating equipment.

Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.

Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54-1996/ANSI Z223.1-1996 and the Installation Standards, Warm Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. In Canada, refer to the CAN/CGA-B149.1- and

REGISTERED QUALITY SYSTEM

Fig. 1ÐMultipoise Furnace in Upflow Orientation

.2-M95 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC). Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls.

Recognize safety information. This is the safety-alert symbol Fig. 1ÐMultipoise Furnace in Upflow Orientation . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 101

Catalog No. 535-745

Printed in U.S.A.

Form 58MXA-6SM

Pg 1

5-99

Replaces: 58MXA-5SM

Tab

6a

8a

 

 

 

 

 

 

 

Page 1
Image 1
Carrier 58MXA instruction manual Service and Maintenance Instructions, →For Sizes 040Ð140, Series, Safety Considerations