Carrier 90MA/MF/MU manual 90MA/MF Physical Data --Refrigerant 134a, R--134a --English Units

Models: 90MA/MF/MU

1 24
Download 24 pages 35.49 Kb
Page 10
Image 10

Table 3 90MA/MF Physical Data -- Refrigerant 134a

 

 

 

 

 

 

 

 

 

 

 

 

R--134a -- English Units

 

R--134a -- Metric Units

BASE UNIT 90MA/MF

UNITS

308

 

312

 

308

 

312

 

English (Metric)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL CAPACITY

Tons (kW)

5.5

 

8

 

19.3

 

28.1

OPERATING WEIGHT

 

 

 

 

 

 

 

 

Base Unit

Pounds (kg)

895

 

950

 

406

 

431

Discharge Plenum

Pounds (kg)

50

 

50

 

22.7

 

22.7

COMPRESSOR TYPE -- Reciprocating

 

Semi--

Hermetic

 

Semi--

Hermetic

Quantity of Cylinders

 

4

 

6

 

4

 

6

Quantity of Unloading Cylinders

 

0

 

2

 

0

 

2

Quantity of Capacity Steps

 

1

 

2

 

1

 

2

DISCHARGE PRESSURE SWITCH

 

 

 

 

 

 

 

 

Opens

psig (kPa)

 

335￿10

 

2310￿69

 

Closes

psig (kPa)

 

235￿20

 

1620￿138

 

SUCTION PRESSURE SWITCH

 

 

 

 

 

 

 

 

Opens

psig (kPa)

 

7￿3

 

48￿21

 

Closes

psig (kPa)

 

22￿5

 

152￿35

 

OPERATING CHARGE

pounds (kg)

11.2

 

10

 

5.1

 

4.5

CONDENSER

 

 

 

 

 

 

 

 

Number & Type

 

1....Tube In Tube

 

1....Tube In Tube

Water Volume

gallon (liter)

 

2.42

 

9.2

 

EVAPORATOR AIR FAN

 

Adjustable, Belt Driven Centrifugal: 1750 RPM Motor @ 60 Hz

Nominal Flow

cfm (m3/h)

3000

 

4000

 

4245

 

5660

Standard Speed Range

RPM

495--700

 

600--850

 

412--583

 

500--708

Maximum Allowable RPM

 

 

 

1050

 

 

 

Belt Quantity / Pulley Pitch Diameter

inches (cm)

1 / 8.5

 

1 / 7.0

 

1 / 21.6

 

1 / 17.8

Motor Pulley Pitch Diameter Range

inches (cm)

 

2.4 to 3.4

 

6.1 to 8.6

 

Motor Nominal Rating(@60 Hz)...Frame Size

 

 

 

 

 

 

 

 

Standard

horse power

1...56

 

2...56

 

.75 / 56

 

1.5 / 56

Alternate (See Note 1)

horse power

2...56

 

3...56

 

1.5 / 56

 

2.2 / 56

Alternate (See Note 1)

horse power

3...56

 

----

 

2.2 / 56

 

----

EVAPORATOR COIL

 

 

3/8

OD(0.95) cm, Copper

Tubes, Aluminum

Fins

 

Tube Type

 

 

 

Prime

 

 

 

Quantity of Rows...fin Spacing

fins/inch(cm)

 

3...12.5

 

3...14.9

 

Face Area

sq ft (sq m)

7.3

 

8.5

 

0.68

 

0.79

RETURN AIR FILTERS

 

 

 

Factory Supplied, Cleanable

 

Quantity...Size

inches (cm)

4...16 x 20 x 1

 

4...40.6 x 50.8 x 2.5

CONDENSER CONNECTIONS

 

 

 

 

 

 

 

 

Water Inlet (bottom) & Outlet (top)

inches FPT

1

 

1

 

1

 

1

Maximum Working Pressure (refrigerant side)

psig (kPa)

 

400

 

2758

 

CONDENSATE DRAIN CONNECTIONS

inches FPT

 

3/4

 

3/4

 

ACCESSORY HEATING COILS

 

 

 

 

 

 

 

 

HOT WATER

 

 

 

 

 

 

 

 

Quantity of Rows...fin spacing

fins/inch(cm)

2...14

 

2...14

 

2...5.5

 

2...5.5

Face Area

sq ft (m)

6

 

6

 

0.56

 

0.56

Water Inlet (top) & Outlet Connection (bottom)

inches (cm)

 

1--1/4

MPT

 

1--1/4

MPT

 

STEAM

 

 

 

 

 

 

 

 

Quantity of Rows...fin spacing

fins/inch(cm)

1...14

 

1...14

 

1...5.5

 

1...5.5

Face Area

sq ft (m)

6.9

 

6.9

 

0.64

 

0.64

Water Inlet (top) & Outlet Connection (bottom)

inches (cm)

 

1--1/4

MPT

 

1--1/4

MPT

 

LEGEND

 

 

 

 

 

 

 

 

FPT = Female Pipe Thread MPT = Male Pipe Thread

ODF = Outside Diameter Female

 

 

 

NOTES:

1.Motors and drives other than those furnished with unit must be purchased separately. Contact your Carrier Transicold represen- tative.

62--10458--00

4

 

Page 10
Image 10
Carrier 90MA/MF/MU manual 90MA/MF Physical Data --Refrigerant 134a, R--134a --English Units, R--134a --Metric Units