Section 1 — Post Installation Start-up and Adjustments

Carrier Air-cooled 7 kW, 12 kW and 15 kW Generators

1.1BEFORE INITIAL START-UP

Before starting, complete the following:

1.Set the generator’s main circuit breaker to its OFF (or open) position.

2.Set the generator's AUTO/OFF/MANUAL switch to the OFF position.

3.Turn OFF the utility power supply to the transfer switch using the means provided (such as the utility main line circuit breaker).

4.Turn OFF all loads connected to the transfer switch terminals T1 and T2.

5.Check the engine crankcase oil level and, if necessary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.

6.Check the fuel supply. Gaseous fuel lines must have been properly purged and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff valves in the fuel supply lines must be open.

Never operate the engine with the oil level

!below the “Add” mark on the dipstick. Doing this could damage the engine.

1.2CHECK TRANSFER SWITCH

OPERATION

Refer to Section 3.5, of the owner’s manual for manual operation procedures.

DANGER

Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.

5.Use an accurate AC voltmeter to check utility power source voltage across transfer switch terminals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.

6.Check utility power source voltage across terminals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to-neutral voltage should be 120 volts AC.

7.When certain that utility supply voltage is compatible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transfer switch.

8.On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL. The engine should crank and start.

9.Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or CLOSED) position.

DANGER

Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dangerous and possibly fatal electrical shock.

10.Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal lugs E1 and E2. Voltage should be 242-252 volts; frequency should read about 61-63 Hertz.

11.Connect the AC voltmeter test leads across terminal lug E1 and neutral; then across E2 and neutral. In both cases, voltage reading should be 121-126 volts AC.

12.Set the generator’s main circuit breaker to its OFF (or open) position. Let the engine run at no-load for a few minutes to stabilize internal engine generator temperatures.

13.Set the generator's AUTO/OFF/MANUAL switch to OFF. The engine should shut down.

1.3ELECTRICAL CHECKS

Complete electrical checks as follows:

1.Set the generator's main circuit breaker to its OFF (or open) position.

2.Set the generator's Auto/Off/Manual switch to the OFF position.

3.Turn OFF all loads connected to the transfer switch terminals T1 and T2.

4.Turn on the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).

DANGER

NOTE:

It is important not to proceed until certain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment. If frequency is correct, but voltage is high or low, the generator’s voltage regulator requires adjustment.

The transfer switch is now electrically “hot.” Contact with “hot” parts will result in extremely hazardous and possibly fatal electrical shock. Proceed with caution.

4 Carrier

Page 6
Image 6
Carrier ASPAS1CCA015, ASPAS1CCA012 manual Before Initial START-UP, Check Transfer Switch Operation, Electrical Checks

ASPAS1CCA012, ASPAS1CCA015 specifications

The Carrier ASPAS1CCA015 and ASPAS1CCA012 are advanced air conditioning units designed to offer superior climate control in residential and light commercial settings. Both models reflect Carrier's commitment to innovation, energy efficiency, and user comfort.

One of the primary features of these units is their inverter technology. This smart technology adjusts the compressor speed in real-time, allowing the system to operate efficiently and maintain a consistent temperature. This results in reduced energy consumption and lower utility bills while providing a more comfortable indoor environment.

The ASPAS1CCA015 and ASPAS1CCA012 also include a state-of-the-art air filtration system. These units are equipped with a high-efficiency particulate air (HEPA) filter that effectively captures dust, allergens, and pollutants. This feature contributes to improved indoor air quality, making them ideal for allergy sufferers and those concerned about indoor air pollution.

In terms of performance, both models deliver impressive cooling and heating capacities. The ASPAS1CCA015 has a cooling capacity of 15,000 BTUs, while the ASPAS1CCA012 offers a cooling capacity of 12,000 BTUs. This range makes them suitable for various room sizes, ensuring effective temperature management whether during scorching summers or chilly winters.

A user-friendly digital thermostat and Wi-Fi connectivity are additional features that enhance the usability of these models. Homeowners can control their air conditioning systems remotely via smartphones or tablets, enabling them to adjust settings for optimum comfort and efficiency even when they are not at home.

The units are designed with quiet operation in mind. They utilize advanced silencing technologies, ensuring that noise levels remain low, allowing for peaceful environments during night-time or in quiet settings. This is particularly beneficial for bedrooms, nurseries, or offices where distraction-free air conditioning is essential.

Moreover, both models are compliant with the latest standards for energy efficiency, earning high SEER (Seasonal Energy Efficiency Ratio) ratings. This not only promotes environmental sustainability but also aligns with governmental incentives aimed at reducing energy consumption.

In summary, the Carrier ASPAS1CCA015 and ASPAS1CCA012 are equipped with cutting-edge technologies and features that make them reliable and efficient air conditioning solutions. With their inverter technology, advanced filtration systems, remote connectivity, and quiet operation, these units represent a combination of comfort, convenience, and environmental responsibility that meets the needs of modern users.