Carrier CPLPCONV006A00 installation instructions LowNOx Baffle Location, Firing Tube

Models: CPLPCONV006A00

1 8
Download 8 pages 56.33 Kb
Page 1
Image 1
Installation Instructions

Small Packaged Products Standard Altitude Only 0–2000 ft Accessory LP Conversion Kit

Cancels: IIK 582A-18-6

IIK 582A-18-7

 

1-01

Installation Instructions

60,000–130,000 Btu/hr

Part Number: CPLPCONV006A00 2 to 5 Tons

NOTE: Read the entire instruction manual before starting the installation.

This symbol indicates a change since the last issue.

Firing Tube

SAFETY CONSIDERATIONS

Installing and servicing air conditioning equipment can be hazard- ous due to system fuels. Only trained and qualified personnel should install, service, or repair air conditioning equipment.

Untrained personnel can perform basic maintenance functions such as cleaning coils, or cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, on tags, and on labels attached to the unit.

Recognize safety information. This is the safety-alert symbol 60,000–130,000 Btu/hr . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available.

Before converting a unit to LP, remove the burner assembly and inspect the heat exchanger tubes. If there are V-shaped NOx baffles installed in the firing tubes (See Fig. 1). THEY

MUST BE REMOVED PRIOR TO CONVERTING

THIS UNIT TO LP. Discard the baffles after removal.

This conversion kit is to be installed by qualified service personnel in accordance with these instructions and all codes and requirements of the authority having jurisdiction, and in Canada, in accordance with the requirements of the CAN/CGA (Canadian Gas Association) B149.2 Installation Code. Failure to follow these instructions could result in serious injury, property damage or death. The qualified agency performing this work assumes responsibility for this conversion.

 

 

NOx Baffle

 

 

C00151

 

Fig. 1–Low NOx Baffle Location

 

 

This unit is designed to operate at 3.5 in. wg (±0.3 in. wg) of

 

 

 

 

 

 

manifold pressure with liquid propane (LP) gas. Exceeding

 

 

 

this pressure may result in explosion, injury or death.

 

 

 

 

 

INTRODUCTION

 

These instructions cover the installation of a liquid propane

 

conversion kit on models 48GS, 582A, PY1P-B, 48GX, 583A,

 

PY2P-B, 48GP, and 583B that are equipped with a White Rodgers

 

combination automatic gas valve regulator.

 

 

DESCRIPTION AND USAGE

 

This kit is applicable to units with heating inputs from 60,000 to

 

130,000 Btu/hrinstalled at standard altitudes from 0 ft to 2000 ft.

 

It cannot be used for high altitude installations or on units with

 

heating inputs of 40,000 Btu/hr. High altitude conversions

 

(2001–6000 ft) should use kit #CPLPCONV007A00. All conver-

 

sions of 40,000 Btu/hr units should use Kit

 

#CPCLPCONV008A00 (applicable for any altitude from 0 ft to

 

6000 ft).

 

 

INSTALLATION

Before performing service or maintenance operations on unit, turn off gas supply first, then the main power switch to unit. Electrical shock could cause serious injury or death. TAG DISCONNECT SWITCH WITH SUITABLE WARNING LABEL.

1. Turn off gas supply first, then power to unit.

2.Remove the front access panel from unit.

3.Disconnect the gas pipe from the gas valve.

4.Disconnect orange sparker cable at the ignition control.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 101

Catalog No. 534-80021

Printed in U.S.A.

Form 48-15SI

Pg 1

1-01

Replaces: 48-14SI

Tab

1a

1a

 

 

 

 

 

 

 

Page 1
Image 1
Carrier CPLPCONV006A00 installation instructions LowNOx Baffle Location, Installation Instructions, Firing Tube