ODSHR Outdoor Woodburning Fireplace

Air Space Clearances

Combustible framing material MUST NOT pen- etrate AIR SPACE (shaded areas)

2"

Standoff

³⁄" Air Space to Sides

Finished Wall

Noncombustible Decorative Fac- ing

Must be Sealed with Noncombustible Material

Stud

2 x 4 Header

Ledge Bracket

Front View

Side View

Surround

Side View

FP1166

Wall

Shield

Only noncombustible mate- rial may be applied as facing to the fireplace surround.

Firestop

³⁄" Air Space to Back

³⁄" Air Space to Sides

0" Clearance to Floor

Hearth Extension

FP559SHR

Fig. 21 Fireplace surround flush with finished wall.

Finished Wall

Stud

 

 

2 x 4 Finished

Noncombustible

Header

 

Decorative Facing

Covered Wall

 

Must be Sealed with

Ledge Bracket

Noncombustible

 

Material

 

Surround

FP1167

 

Fig. 20 Minimum clearances to combustibles.

Finish Wall

Finish the wall with material of your choice. Do not install a combustible mantel shelf less than 12"

(305 mm) from the top of the fireplace opening. Do not install a mantel face plate less than 6" (154 mm) from top of fireplace opening. (Fig. 24) If a combus- tible material is used below a flat mantel shelf, consult your local building codes for minimum clearance from top of fireplace opening to bottom of mantel shelf.

All joints (top, bottom and sides) where wall or deco- rative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figs. 21-23)

NOTE: No side wall protection is required for fireplaces installed at 45° to two (2) side walls (corner installa- tion).

Fig. 22 Facing on fireplace surround flush with finished wall.

CAUTION:

Screen Rail

Do Not Place Finish-

 

ing Material Beyond

 

These Edges or Cover

 

Air Inlets

Hearth

FP1168

Fig. 23 Finishing front of fireplace.

14