ODSHR Outdoor Woodburning Fireplace

Side Wall Protection

40"

Min.

Adjacent combustible side walls that are within dimen- sions shown in Figure 25 of fireplace opening must be protected with CFM Corporation Wall Shield Model SP40 or a specifically built wall shield described in Figure 26.

The special wall shield design described in Figure 26 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.

Examples of wall shield insulation:

1. Manville - CERAFORM 126, K=.27,

1/2 inches thick

Decorative Non- combustible Rigid Covering

FP838

40" Min.

Noncombustible Insula-

tion

RT = 1.85 Min.

(Manville Ceraform 126

-1/2" Thick or CFM Corporation EH2416 - 1" Thick)

2. CFM Corporation - EH2416, K = .458,

1 inch thick required.

Hearth Installation

A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 27 for mini- mum dimensions and mounting detail.

NOTE: Hearth Extension must not cover the air inlet opening of a fireplace.

The hearth extension described in Figure 27 must be a durable noncombustible material with a minimum (total) Rt value of 1.09; refer to Figure 28 for examples. The overall height (above a combustible floor), depth and width must be as indicated, with the extension centered to the fireplace opening.

Fig. 26 Noncombustible wall shield dimensions.

The top of insulation must be covered with a non-com- bustible decorative covering or a piece of .018” mini- mum sheet metal, to protect hearth extension material. (Fig. 27)

Secure the hearth extension to the floor to prevent shifting, using trim molding or other similar means at three (3) outer edges. Seal crack between the fireplace hearth and hearth extension with a noncombustible material. (Figs. 27, and 29 - 31)

WARNING: HEARTH EXTENSION MUST BE IN- STALLED IN ACCORDANCE WITH FIGURE 24.

Minimum Wall Clearances

WITH

WITHOUT

 

Noncombustible

Noncombustible

Surround Facing

Surround Facing

 

 

Shaded area starts

4" Brick

 

3/4" away from

(Example material)

 

edge of unit

 

 

 

4"

 

18" 14"**

Firebox

18"

39���"

 

Opening

 

32���"**

22" - Min. clearance

 

 

 

to combustible

 

 

 

perpendicular wall

 

 

Side

18" - Min. clearance

Side

Wall

to combustible

Wall

 

perpendicular wall when

 

 

 

using noncombustible wall shield*

 

Combustible material permitted within shaded area.

*Noncombustible wall shield requires 1" CFM Corporation EH2416 insulation (minimum R Value = 1.85) between decorative noncombustible rigid covering and combustible wall. Minimum height and width is 40" x 40".

**Dimension/degree of angle will vary depending on thickness of noncombustible surround facing.

Minimum Hearth Extension Dimensions

(for On-Site Construction)

 

20"

12"

12"

 

 

 

 

66"

 

 

Seal cracks

 

 

May install

between the

 

 

noncombustible

fireplace

 

 

 

decorative

and hearth

 

 

 

covering

extension with

 

 

OR .018" min.

noncombustible

 

 

sheet metal

material

 

Fireplace

 

 

 

 

Hearth

 

4" Min.

 

 

 

 

Combustible

Minimum

Safety strips

 

Floor

Insulation

must overlap

 

 

Value "R":

���" minimum

FP532b

 

 

 

 

Fig. 27 Combustible side wall protection and hearth extension dimensions.

16

20002264

Page 16
Image 16
CFM Corporation ODSHR42 manual Side Wall Protection, Hearth Installation, Examples of wall shield insulation