D. MASTER/SLAVE SETUP PROCEDURE
1. Be sure to turn off both gate operator units.
2. Connect Master and Slave units as described and shown in paragraph C and Figure 15, above.
3. Set Switch S1 on Master and Slave units to your gate configuration according to the table, below.
NOTES
If, before power up, the Master/Slave connection is broken, one of the units is turned off, or one of
the controller boards malfunctions, the gates will operate in stand alone configuration.
If the Master/Slave connection is broken after power up, it prevents either gate from moving.
MASTER UNIT SWITCH S1 SETTINGS AND INPUTS
Gate
Type
SLIDE
ACTION
(Reclose)
TIMER RETRY ATG MASTER TRAP Operator
Inputs
Bi-Parting Unit
Option
System
Optionn
System
Optionn
System
Optionn ON ON Systemp
Bi-Parting
Latch
Unit
Option
System
Optionn
System
Optionn
System
Optionn ON OFF Systemp
Trap Unit
Optiono
Unit
Optiono
Unit
Optiono ON ON ON Unit
Tandem Unit
Optiono
Unit
Optiono
Unit
Optiono OFF ON ON Unit
n: Select AT G, Timer and/or Retry (if desired) from the Master unit and set Slave ATG, Timer and Retry to OFF.
Otherwise, the ATG ON/shorter Reclose Timer/Retry ON in either unit supersedes the other.
o: Master and Slave units can have different settings.
p: Inputs affect both gate operators, so connect to one unit only.
: Inputs affect one gate operator only, so connect inputs separately to each gate operator.
: For safe and reliable operation, this setting MUST be the same for both units (see Appendix A).
SLAVE UNIT SWITCH S1 SETTINGS AND INPUTS
Gate
Type
SLIDE
ACTION
(Reclose)
TIMER RETRY ATG MASTER TRAP Operator
Inputs
Bi-Parting Unit
Option
System
Optionn
System
Optionn
System
Optionn ON OFF Systemp
Bi-Parting
Latch
Unit
Option
System
Optionn
System
Optionn
System
Optionn OFF OFF Systemp
Trap Unit
Optiono
Unit
Optiono
Unit
Optiono No Effect OFF OFF Unit
Tandem Unit
Optiono
Unit
Optiono
Unit
Optiono
Unit
Option OFF OFF Unit
n: Select AT G, Timer and/or Retry (if desired) from the Master unit and set Slave ATG, Timer and Retry to OFF.
Otherwise, the ATG ON/shorter Reclose Timer/Retry ON in either unit supersedes the other.
o: Master and Slave units can have different settings.
p: Inputs affect both gate operators, so connect to one unit only.
: Inputs affect one gate operator only, so connect inputs separately to each gate operator.
: For safe and reliable operation, this setting MUST be the same for both units (see Appendix A).