Grounding
TO PREVENT ELECTRIC SHOCK AND DEATH
FROM INCORRECT GROUNDING WIRE CONNECTION:
Check with a qualified electrician if you are in doubt as to whether the outlet is properly grounded. Do not modify the power cord plug provided with the tool. Do not use the tool if the power cord or
plug is damaged. If damaged, have it repaired by a service facility before use. If the plug will not fit the outlet, have a proper outlet installed by a qualified electrician.
Double Insulated Tools: Tools with Two Prong Plugs
1.Tools marked “Double Insulated” do not require grounding. They have a special double insulation system which satisfies
OSHA requirements and complies with the applicable standards of Underwriters Laboratories, Inc., the Canadian Standard Association, and the National Electrical Code.
2.Double insulated tools may be used in either of the 120 volt outlets shown in the preceding illustration.
(See Outlets for | Outlets for |
Extension Cords
SAFETY
SETUP
1.Double Insulated tools can use either a two or three wire extension cord.
2.As the distance from the supply outlet increases, you must use a heavier gauge extension cord. Using extension cords with inadequately sized wire causes a serious drop in voltage, resulting in loss of power and possible tool damage. (See Table A.)
3.The smaller the gauge number of the wire, the greater the capacity of the cord. For example, a 14 gauge cord can carry a higher current than a 16 gauge cord. (See Table A.)
4.When using more than one extension cord to make up the total length, make sure each cord contains at least the minimum wire size required. (See Table A.)
5.If you are using one extension cord for more than one tool, add the nameplate amperes and use the sum to determine the required minimum cord size. (See Table A.)
6.If you are using an extension cord outdoors, make sure it is marked with the suffix
Canada) to indicate it is acceptable for outdoor use.
7.Make sure the extension cord is properly wired and in good electrical condition. Always replace a damaged extension cord or have it repaired by a qualified electrician before using it.
8.Protect the extension cords from sharp objects, excessive heat, and damp or wet areas.
Table A: RECOMMENDED MINIMUM WIRE
GAUGE FOR EXTENSION CORDS* (120/240 VOLT)
NAMEPLATE | EXTENSION CORD | |||
AMPERES |
| LENGTH |
| |
(at full load) | 25’ | 50’ | 75’ | 100’ |
7.1 – 12.0 | 18 | 14 | 12 | 10 |
12.1 – 16.0 | 14 | 12 | 10 | - |
16.1 – 20.0 | 12 | 10 | - | - |
*Based on limiting the line voltage drop to five volts at
150% of the rated amperes.
OPERATION
Symbology
Double Insulated
Canadian Standards Association
Underwriters Laboratories, Inc.
V~ | Volts Alternating Current |
A | Amperes |
| |
|
|
n0 xxxx/min. | No Load Revolutions |
per Minute (RPM) |
MAINTENANCE
SKU 68316 | For technical questions, please call | Page 7 |