HDS-1 Power Disconnect Switch Kit

for Field Installation in an HVH Series Air Heater

Specifications — Table A

 

 

Electrical Data (60 Hz)

 

Standard

 

 

 

 

 

Contactor

 

 

 

 

 

Model

Volts

Watts

Phase

Amps

Rating (Qty.)

HVH-02-81

208

2,667

1

12.8

 

HVH-02-21

208/240

2000/2,667

1

11.1*

——

HVH-02-71

277

2,667

1

9.6

 

HVH-04-81†

208

4,000

1

19.2

——

HVH-04-83†

3

11.2

30A (1)

 

 

HVH-04-21†

208/240

3,000/4,000

1

16.7*

——

HVH-04-23†

3

9.6*

30A (1)

 

 

HVH-04-71

277

4,000

1

14.5

——

HVH-04-43

480

4,000

3

4.8

30A (1)

HVH-05-81†

208

5,000

1

24.0

——

HVH-05-83†

3

13.8

30A (1)

 

 

HVH-05-21†

208/240

3,750/5,000

1

20.8*

——

HVH-05-23†

3

12.1*

30A (1)

 

 

HVH-05-71

277

5,000

1

18.2

——

HVH-05-43

480

5,000

3

6.0

30A (1)

HVH-07-81†

208

7,500

1

36.1

50A (1)

HVH-07-83

3

20.9

30A (1)

 

 

HVH-07-21†

208/240

5,625/7,500

1

31.1*

30A (1)

HVH-07-23

3

18.1*

30A (1)

 

 

HVH-07-71

277

7,500

1

27.2

30A (1)

HVH-07-43

480

7,500

3

9.0

30A (1)

HVH-10-81†

208

10,000

1

48.0

50A (1)

HVH-10-83

3

27.8

30A (1)

 

 

HVH-10-21†

208/240

7,500/10,000

1

41.7*

30A (1)

HVH-10-23

3

24.0*

30A (1)

 

 

HVH-10-43

480

10,000

3

12.0

30A (1)

HVH-12-83

208

12,500

3

34.8

50A (1)

HVH-12-23

208/240

9,375/12,500

3

30.1*

50A (1)

HVH-12-43

480

12,500

3

15.1

30A (1)

HVH-15-83

208

15,000

3

41.8

50A (1)

HVH-15-23

208/240

11,250/13,000

3

36.2*

50A (1)

HVH-15-43

480

15,000

3

18.1

30A (1)

* Note: 208V amperage is 86% of 240V value.

These models can be field changed from single phase to three phase or three phase to single phase.

GENERAL

This instruction sheet provides information for field installing an HDS-1 Power Disconnect Switch in an HVH Series air heater.

ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could result in personal injury or property dam- age. Power Disconnect Switch must be installed by a qualified person in accordance with the National Electrical Code, NFPA 70.