Chromalox PF455-3 manual General

Models: PF455-3

1 8
Download 8 pages 44.66 Kb
Page 2
Image 2
Figure 8

GENERAL

Limitations: Ductwork must be in accordance with one of the fol-

lowing: Standards of the National Fire Protection Association for the installation of Air Conditioning and Ventilating Systems of other than Resident Type (Pamphlet 90A) or Residential Type Warm Air Heating and Air Conditioning Systems (Pamphlet 90B).

4.Installation near turns. (Refer to Figure 8). If heater must be installed closer than 4 feet from the downstream side of a turn, turning vanes must be installed in the turn. The turning vanes will straighten out the air flow so it will be uniform over the face of the heater.

Location: Chromalox Duct Heaters may be located anywhere in the duct system.

NOTE: The minimum distances shown are limitations. Wherever possible, locate as far away from these limits as practical. In any case, this distance with any required airflow correction must be sufficient to accomplish even air flow at a velocity equal to, at least, the minimum stated on the heater nameplate.

1.Installation near heat pump, central air conditioner, filters or humidifier. (Refer to Figure 5).

Duct Heater

Duct Heater Here or Here

2 Ft.

Min.

Air

Flow

 

4 Ft.

Min.

Air

Flow

4 Ft.

Min.

Heat Pump,

Figure 8

5.Installation with duct transitions in some air distribution sys- tems, the duct heater may be considerably larger than the duct- work and the duct area must be increased by a sheet metal tran- sition. The slope of the transformation piece on the upstream side of the equipment is limited to 30° as indicated in Figure 9. On the leaving side, the slope should not be more than 45°.

Central Air Conditioner,

Filters or Humidifier

Figure 5

2.Installation near air handler discharge. (Refer to Figure 6).

Duct Heater

Air

Flow

30"

Max.

Air

Flow

30°

4 Ft. Min.

Duct Heater

45°

45°

Max.

4 Ft. Min.

4 Ft.

Min.

Air Handler

Figure 6

3.Installation in branch duct take-off. (Refer to Figure 7).

Air

Flow

 

4 Ft. Min. Straight Section

Duct Heater

Figure 7

Figure 9

6.Do not insulate control or terminal box. (Refer to Figure 10).

 

External

 

Insulation

Top of Duct

Duct Heater

 

Leave Control

 

Box Uninsulated

 

Figure 10

-2-

Page 2
Image 2
Chromalox PF455-3 manual General