Send documentation comments to nexus5kdocs@cisco.com
2-16
Cisco Nexus 5000 Series Hardware Installation Guide
OL-15902-01
Chapter 2 Installing the Cisco Nexus 5000 Switch
Grounding the Chassis
Figure 2-8 Location of System Ground on a Cisco Nexus 5000 Switch
Warning
When installing or replacing the unit, the ground connection must always be made first and
disconnected last.
Statement 1046
Caution Grounding the chassis is required if you are using DC power supplies, even if the rack is already
grounded. A grounding pad with two threaded M4 holes is provided on the chassis for attaching a
grounding lug. The ground lug must be NRTL listed. In addition, the copper conductor (wires) must be
used and the copper conductor must comply with NEC code for ampacity.
To attach the grounding lug and cable to the chassis, follow these steps:
Step 1 Use a wire-stripping tool to remove approximately 0.75 inches (19 mm) of the covering from the end of
the grounding cable.
Step 2 Insert the stripped end of the grounding cable into the open end of the grounding lug.
Step 3 Use the crimping tool to secure the grounding cable in the grounding lug.
1ESD socket (on switch) 4Screws, M4, with square cone
washers
2ESD plug 5NRTL listed grounding lug
3Grounding cable 6Close-up of grounding pad on
switch
186483