Cooper Lighting dimensions Cooper Lighting - Sure-Lites, CC3 CC4 CC5 CC6, Commercial

Models: CC5

1 1
Download 1 pages 39.05 Kb
Page 1
Image 1
Commercial

Commercial

COOPER LIGHTING - SURE-LITES®

D E S C R I P T I O ND I M E N S I O N S

EMERGENCY LIGHTS

CC3

CC4

CC5

CC6

C o n t r a c t o r ’s C h o i c e

E M E R G E N C Y L I G H T

The CC Series Contractor’s Choice Emergency Lighting Unit is the ideal choice when a simple installation and

areasonable cost are required. Its contemporary round corner styling, designer white finish, and consistent family appearance enables it to blend with any decor. The components are injection molded from tough polycarbonate materials which resist discoloration due to age and ultraviolet radiation.

13"

(330mm)

6 3/8"

(162mm)

17 1/2"

(445mm)

4 3/4"

(121mm)

SURE-LITES

Dual-voltage input

120/277VAC, 60Hz, isolation

transformer

Injection-molded, color-

stable, high-impact UL-94-5V

rated polycarbonate housing

and mounting plate (Housing

is tethered to mounting

plate)

Designer-white textured

finish

• Two PAR36 type lamps in

fully adjustable high-impact

polycarbonate lampholders

• Sealed lead calcium

maintenance free battery

E L E C T R I C A L R AT I N G S

 

 

Rated Wattage to 87 1/2% of rated D.C. Voltage

Lamp Information

 

Model

DC Voltage

1 1/2 hours

2 hours

3 hours

4 hours

Type

Wattage

Number

CC3

6

10.8

7.2

-

-

Incandescent

5.4

29-121

CC3 NC

6

16

-

-

-

Incandescent

5.4

29-121

CC4

6

18

15

10

8

Incandescent

9

29-84

CC4 NC

6

18

 

 

 

Incandescent

9

29-84

CC5

6

27

24

18

14

Incandescent

9

29-84

CC5 NC

6

24

 

 

 

Incandescent

9

29-84

CC6

6

32

-

-

-

Incandescent

9

29-84

O R D E R I N G I N F O R M AT I O N

S A M P L E N U M B E R : C C 5 W H S D

• Cutouts provided for surface

conduit on top

• Universal J-box mounting

pattern, keyhole slots

• Remote Capability

CC5, CC6

Line-Latching, Solid-State

Voltage Limited Charger,

Solid-State Switching, Low-

Voltage Disconnect,

Brownout Circuit,

Overload/Short Circuit

Protection, Test switch/power

Indicator light

• UL 924 Listed, UL Damp

Location Listed (CC5SD

Model

Number

CC3

CC3NC(4)

CC4

CC4NC(4), (6)

CC5

CC5NC(4), (6)

CC6

Housing

Finish

(Must be specified) WH=White BK=Black

Voltage

Blank=120/277

347=120/347 VAC

Options

(add as suffix)

MRT=MR16 Heads (5W Standard CC3, CC3NC; 9W Standard CC4, CC5, and CC6)

SQ=Square Head (5.4W Standard)

A =Ammeter (1)

SD=Self-Diagnostics(3), (5), (6) V=Voltmeter(1)

TDM=Time Delay Monitor

Alternate Lamps(2)

Other Options(2)

Accessories

(Order separately) WG1 =Wire Guard WG2 =Wire Guard (use for heads adjusted at 45° or greater) VS1=Polycarbonate

Vandal Shield

VS1WP=Polycarbonate Vandal Shield Weather Resistant

CSK120=Cord Set 120V

Only), Life Safety NFPA 101,

CSA Certified, NEC/OSHA,

most state and local codes

E n e r g y D a t a

 

Input Current (Max.):

 

 

 

 

 

Model No.

120V

277V

347V

CC3

.12A

.05A

.01A

CC4

.12A

.05A

.01A

CC5

.13A

.06A

.06A

CC6

.13A

.06A

.06A

616

COOPER LIGHTING

(1)Provision for one meter only. (2)Consult your Cooper Lighting Representative. (3)Not available w/CC6. (4)NC=Nickel Cadmium Battery. (5)CC5SD is

damp location standard. (6)CC4NC, CC5NC not available in SD.

Page 1
Image 1
Cooper Lighting dimensions Cooper Lighting - Sure-Lites, CC3 CC4 CC5 CC6, Commercial, Emergency Lights