Metalux • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801 10/06/2008 12:19:15 PM
Specifications and Dimensions subject to change without notice.
ADF070947

ORDERING INFORMATION

PI OPTION ORDERING INFORMATION

SHIPPING INFORMATION

SAMPLE NUMBER: MB-132-NB-UNV-EB81- U
Number of Lamps
(Not included)
1=1 Lamp
2=2 Lamps
Lamp Types
32=32W T8 (4')Lamp
Voltage
UNV=Universal 120-277 Voltage
UNC=Universal 347/480 Voltage(4)
Options
GL=Single Element Fuse
GM=Double Element Fuse
EL=Emergency Installed (2)
Tandem
Blank=
4' Length
8T=
8' Length
Series
MB= Micro-Bay
Ballast Type(1)
T8 Systems
EB8 =T8 Electronic Instant Start.(5)
Total Harmonic Distortion < 10%
EB8 /PLUS=T8 Electronic Instant Start.(5)
High Ballast Factor >1.15.
Total Harmonic Distortion < 10%
ER8 =T8 Electronic Program Rapid Start.(5)
Total Harmonic Distortion < 10%
ER8 /PLUS=T8 Electronic Program Start.(5)
High Ballast Factor >1.15.
Total Harmonic Distortion < 10%
DIM=Consult Factory(7)
Options
PI/CPI=Plug-In (1, 2 or 3)
C3=3' Power Cord
C6=6' Power Cord
PC3-=3' Power Cord & Plug (Specify Voltage)(3)
PC6-=6' Power Cord & Plug (Specify Voltage)(3)
Packaging
U=Unit Pack
Reflector
FB=Focus Beam
TB=Task Beam (Medium)
NB=Normal Beam
No. of Ballast
1 or 2
No. of
Ballast
1 or 2
No. of Ballast
1 or 2
Accessories(order separately)
GRIPPLE-Y- =Y Mounting Toggle, #2 Cable (Specify 10' or 30')
(Row Mount)
GRIPPLE-TOGGLE- =Single Toggle, #2 Cable (Specify 10' or 30')
(Stand-alone)
MB-EXT-LONG-CONN-KIT-U=Rigid Connector Support for
Continuous Channel Installation
MS=Aisle Coverage Motion Sensor(3) (6)
MSO=360° Coverage Motion Sensor(3) (6)
MB-SENSOR-KIT-END/MT-U=Aisle Coverage Motion Sensor, End
Mount Hardware, 120/277V
MB-SENSOR-KIT-END/480V-U=Aisle Coverage Motion Sensor,
End Mount Hardware, 480V
NOTES: (1)Products also available in non-US voltages and frequencies for international markets. (2)Voltage to be specified with emergency ballast option.(3)Voltage must be specified when ordered with plugs, motion sen-
sors or emergency ballasts. (4)2 lamp ballast configurations only in UNC versions. (5)ER8 and EB8 ballast systems suitable for operation in ambient environments up to 50°C. (6)Shipped separately. (7)Dimming ballast must
be specified at time of order.
No. of
Ballast
1 or 2

Catalog Circuit

Number Number of Wired To

Suffix Circuits Ballast

PI 1 BLK 1 Black

PI 2 BLU 2 Blue

PI 2 BLK 2 Black

PI 3 RED 3 Red

PI 3 BLU 3 Blue

PI 3 BLK 3 Black

BLK=Black Hot
PI1= Single
Circuit
NG= No Ground (ground provided
by fixture body)
WG= With Ground (separate
ground wire in harness)

PI1 - Single Circuit Plug-In

SAMPLE NUMBER: PI1BLK-WG
BLK=Black Hot
BLU=Blue Hot
PI2= Two
Circuit
NG= No Ground
(ground provided by
fixture body)
WG= With Ground
(separate ground wire
in harness)

P I 2 - Tw o C i r c u i t P l u g - I n

SAMPLE NUMBER: PI2BLK-WG
Leave Blank=Single
Neutral
/WHT=White Neutral
/GRY=Gray Neutral
Leave Blank=Single
Neutral
2NEU=Two Neutrals
BLK=Black Hot
BLU=Blue Hot
RED=Red Hot
PI3= Three
Circuit
NG= No Ground (ground provided
by fixture body)
WG= With Ground (separate
ground wire in harness)

PI3 - Three Circuit Plug-In

SAMPLE NUMBER: PI3BLK-WG
Leave Blank=Single
Neutral
/WHT=White Neutral
/GRY=Gray Neutral
Leave Blank=Single
Neutral
2NEU=Two Neutrals
For complete product data, reference the Fluorescent Specification binder. Specifications & dimen-
sions subject to change without notice. Consult your Cooper Lighting Representative for availabili-
ty and ordering information.

Catalog Numbering System

The PI System is available in sections up to 8' in length for continuous row wiring by simply plugging the sections

together. Each PI section is factory wired to the ballast leads. Color coding of wires is as follows:

PI-1 = One Circuit - 2 Wires: one black, one white

PI-2 = Two Circuits - 3 Wires: one black, one blue, one white

PI-3 = Three Circuits - 4 wires: one black, one blue, one red, one white

When ordering the PI2/PI3 System it is necessary to specify the number ofxtures required for each circuit. Each circuit in

fixture must be ordered as a separate line item, with a different hot wire color specified. All wiring to external feeds, using

cord or cord & plug, are responsibility of installing licensed contractor. Cord and cord & plug sets must be ordered

separately if PI option is chosen.

.sbl 6231-BM
Catalog No. Wt.