Costar instruction manual COSTAR MODEL 12SIR Carbon Monoxide Gas Alarm, Mark Goldstein, Ph.D

Models: 12SIR

1 7
Download 7 pages 15.86 Kb
Page 1
Image 1
COSTAR MODEL 12SIR

Instruction Manual: COSTAR® 12SIR, 12V System CO Alarm

COSTAR MODEL 12SIR

Carbon Monoxide Gas Alarm

12V System

INSTALLATION and OPERATING

INSTRUCTIONS

UL2075 LISTED

CARBON MONOXIDE GAS ALARM

Dear New COSTAR® 12SIR Owner,

Congratulations as you have taken steps to help insure the health and life safety of you and your family. We are proud to offer you our unique, patented CO Sensor technology that detects CO in a manner similar to the human body's response. The COSTAR® 12SIR is an ideal and low-cost way of warning you of both the acute and chronic effects of CO poisoning.

Please read this owner's manual carefully so you will have a better understanding of the effects of CO poisoning and the COSTAR® 12SIR Alarm, as we work together pursuing a safer, healthier indoor air quality for us all.

To your good health and safety,

Mark Goldstein, Ph.D.

President

Quantum Group Inc.

1.0GENERAL DESCRIPTION

This CO alarm is suited for residences, motels, hotels, and commercial or industrial system applications. The 12SIR is designed for 4- 6 wire connection to 12VDC alarm system control panels.

Reference: UL Listed Household Fire and/or Burglary Panel with auxiliary signaling zones. Connect to signaling zones which can be designated for CO alarm use only.

2.0PRODUCT DATA

2.1Sensitivity Setting:

Unit will alarm at 150 ppm CO within 50 minutes.

2.2Power:

12VDC nominal

2.3Current Draw:

Standby 20 microAmp. Alarm 60 mA. Trouble 30 mA.

2.4Field Wiring:

14-22 AWG

2.5Relay Contacts:

Dry form 'C' (100 microAmp – 0.1A, 12VDC) non-latching

2.6Operating Temperature:

4.4° C – 37.8° C (40° F - 100° F)

2.7Operating Humidity:

15-95% RH

2.8Horn (Sounder) Loudness: 85 db @ 10 ft (3.3 meters)

3.0APPROVALS

Listed by Underwriters Laboratories Inc. to the Category Gas and Vapor Detectors and Sensors (FTAM).

QGI P/N 099-0066-01 REV 10/26/01 Page 1 of 7