Figure 25: Common Near-Boiler Piping MistakesTable 6: Steam Boiler Riser & Header Pipe SizesSteam Steam Return Condensate Equalizer
Boiler Header Riser Pipe Header Return Pipe Pipe
Model Size (in) Quantity Size (in) Size (in) Quantity Size (in) Quantity Size (in)
32-380 3 1 3 1 1/2 1 1 1/2 1 2
32-475 3 1 3 1 1/2 1 1 1/2 1 2
32-570 4 2 3 1 1/2 1 1 1/2 1 2
32-665 4 2 3 2 1 2 1 2 1/2
32-760 4 2 3 2 1 2 1 2 1/2
32-855 4 2 3 2 1 2 1 2 1/2
32-950 5 2 3 2 1 2 1 2 1/2
32-1045 5 3 3 2 1 2 1 2 1/2
32-1140 5 3 3 2 1/2 1 2 1 2 1/2
32-1235 5 3 3 2 1/2 1 2 1 2 1/2
32-1330 5 3 3 2 1/2 1 2 1 2 1/2
32-1425 5 3 3 2 1/2 1 2 1 2 1/2
32-1520 6 3 3 2 1/2 1 2 1 2 1/2
32-1615 6 4 3 2 1/2 1 2 1 2 1/2
32-1710 6 4 3 2 1/2 1 2 1 2 1/2
32-1805 6 4 3 2 1/2 1 2 1/2 1 3
32-1900 6 4 3 2 1/2 1 2 1/2 1 3
32-1995 6 4 3 3 1 2 1/2 1 3
32-2090 6 5 3 3 1 2 1/2 1 3
32-2185 8 5 3 3 1 2 1/2 1 3
32-2280 8 5 3 3 1 2 1/2 1 3
32-2375 8 5 3 3 1 2 1/2 1 3
32-2470 8 5 3 3 1 2 1/2 1 3
32-2565 8 5 3 3 1 3 1 4
32-2660 8 6 3 3 1 3 1 4
32-2755 8 6 3 3 1 3 1 4
32-2850 8 6 3 4 1 3 1 4
Note: 1. The pipe sizes listed above are nominal trade sizes for Schedule 40 pipe.