8) Multiple Tankless Heaters - If two tankless heaters are installed in the boiler, it is recommended that each heater be

installed in parallel with its own mixing valve, relief valve, flow restrictor, etc.. This will permit either heater to be

removed from service for maintenance while still providing some domestic water to the building.

Tankl ess Heater
Model Number For Use In
Boile rs
Continuous Draw
Heat er Rat ings
40° - 140° Rise
with 200°F Boiler
Temperature
Pressure Drop
Through Heater
(psi)
Minimum
Num ber of
Sections
Required Per
Heat er
Clearance
Requirement
For He ater
Rem ov al
T-1 All Sizes 4.5 GPM 8.8 5 27"
T-2 All Sizes 5.0 GPM 18.0 6 32"
T-3 32-665 & Larger 6.0 GPM 1.2 8 42"
All Series 32 boilers are furnished with left and right heater endsections. Itis possible to installa heater in both ends
provided the number of sec tions inthe boiler in not less than the sum of the number of sections required f or each
heater as indicated in the table. Example: T2 + T3 = 6 + 8 = 14 section or larger boiler.
Table 9: Tankless Heater SpecificationsFigure 32: Tankless Heater Piping