Crown Boiler BWC090, BWC120, BWC070 installation manual 8 VENT/ AIR INTAKE FITTING EQUIVALENT LENGTH

Models: BWC120 BWC070 BWC090

1 27
Download 27 pages 52.29 Kb
Page 10
Image 10
TABLE 7.8: VENT/ AIR INTAKE FITTING EQUIVALENT LENGTH

TABLE 7.8: VENT/ AIR INTAKE FITTING EQUIVALENT LENGTH

VENT FITTING

EQUIVALENT LENGTH (ft)

 

 

60/100mm 90° CONCENTRIC ELBOW

4.5

 

 

60/100mm 45° CONCENTRIC ELBOW

4.0

 

 

80/125mm 90° CONCENTRIC ELBOW

8.5

 

 

80/125mm 90° SWEEP CONCENTRIC ELBOW

5.5

 

 

80/125mm 45° CONCENTRIC ELBOW

3.0

 

 

80/125mm 90° CONCENTRIC SUPPORT ELBOW

8.5

 

 

3” SINGLE WALL 90° ELBOW

5.5

 

 

3” SINGLE WALL 45° ELBOW

4.0

 

 

TABLE 7.9: SUMMARY OF VERTICAL VENTING OPTIONS

VENT OPTION #

CLASSIFICATION USED IN THIS MANUAL

ILLUSTRATED IN FIGURE

VENT PIPE PENETRATION THROUGH STRUCTURE

AIR INTAKE PIPE STRUCTURE THROUGH STRUCTURE

VENT PIPE SIZE

AIR INTAKE PIPE SIZE

LENGTH

VENT

BWC070

BWC090

 

 

MAXIMUM

INLET

BWC120

BWC120

 

 

BWC070

 

 

BWC090

LENGTH

VENT

BWC070

BWC090

 

 

MINIMUM

INLET

BWC120

BWC070

 

 

 

 

BWC090

 

 

BWC120

VENT TERMINAL

AIR INTAKE TERMINAL

VENT MATERIAL

AIR INTAKE MATERIAL

5

6

VERTICAL

VERTICAL

TWIN PIPE

CONCENTRIC

7.10

7.11

ROOF

ROOF

ROOF

ROOF

3”

80/125 mm CONCENTRIC

3”

 

49.5ft

49.5ft

49.5ft

49.5ft

49.5ft

49.5ft

49.5ft

49.5ft

49.5ft

49.5ft

49.5ft

49.5ft

2ft

2ft

2ft

2ft

2ft

2ft

2ft

2ft

2ft

2ft

2ft

2ft

STRAIGHT TERMINAL

 

BY VENT SYSTEM MFR.

CROWN #230532

(TABLE 7.5)

CONCENTRIC TERMINAL

 

3” 180° ELBOW

(TABLE 7.4b)

(FIGURE 7.10)

 

APPROVED STAINLESS

CROWN 80/125 mm VENT

STEEL VENT SYSTEM

COMPONENTS SHOWN IN

GALVANIZED OR PVC

TABLE 7.4b

 

 

 

19

Page 10
Image 10