b.Find the volume of the room in cubic feet. The volume of the room in cubic feet is: Length (ft) x width (ft) x ceiling height (ft)

In calculating the volume of the boiler room, consider the volume of adjoining spaces only if no doors are installed between them. If doors are installed between the boiler room and an adjoining space, do not consider the volume of the adjoining space, even if the door is normally left open.

c.Divide the volume of the boiler room by the input in thousands of BTU/hr. If the result is less than 50, the boiler room is a confined space.

Example:

An AWI162EN and a water heater are to be installed in a room measuring 6 ft - 3 in x 7 ft with an 8 ft ceiling. The water heater has an input of 30000 BTU/hr:

Total input in thousands of BTU/hr = (162000 BTU/hr + 30000 BTU/hr)/1000 = 192 Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft3

350/192 = 1.82. Since 1.82 is less than 50, the boiler room is a confined space.

2)Unconfined Space - Natural infiltration into the boiler room will normally provide adequate air for combustion and ventilation without additional louvers or openings into boiler room.

3)Confined Space - Provide two openings into the boiler room, one near the floor and one near the ceiling. The top edge of the upper opening must be within 12” of the ceiling and the bottom edge of the lower opening must be within 12” of the floor (Figure 3).

Each opening must have a free area of 1 square inch per 1000 BTU/hr input of all gas burning appliances in the boiler room. The minimum opening dimension is 3 inches. Minimum opening free area is 100 square inches per opening.

If the total volume of both the boiler room and the room to which the openings connect is less than 50 cubic feet per 1000 BTU/hr of total appliance input, install a pair of identical openings into a third room. Connect additional rooms with openings until the total volume of all rooms is at least 50 cubic feet per 1000 BTU/hr of input.

The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are used, they must be no finer than ¼” (4 x 4) mesh.

If providing openings into adjacent rooms is undesirable, combustion and ventilation air can be brought into the boiler room from outdoors. See the instructions under “For Buildings of Unusually Tight Construction”.

FIGURE3:BOILERINSTALLEDINCONFINEDSPACE,

ALL AIR FROM INSIDE

8

6

Page 8
Image 8
Crown Boiler AWI262, TWI095, TWI128, TWI061, TWI162, AWI061, AWI195, AWI162, AWI229, AWI037, AWI128, AWI095, AWI295 Example

AWI262, AWI095, TWI095, AWI195, AWI037 specifications

Crown Boiler is a renowned name in the heating industry, providing high-quality, efficient heating solutions that cater to various residential and commercial needs. Among its impressive lineup, the AWI and TWI series stand out for their design, technology, and performance.

The Crown Boiler AWI061 and TWI061 are part of the Hydronic Boiler range, designed to deliver efficient hot water heating. The AWI series features an advanced pressure-jet design that allows it to operate with exceptional fuel efficiency, reducing operating costs for homeowners and businesses alike. Additionally, these models come equipped with an integrated pump system that ensures a consistent supply of hot water, making them ideal for both space heating and domestic hot water applications.

Meanwhile, the AWI162 and AWI128 models are engineered for higher output, addressing larger heating needs without compromising efficiency. These models showcase a robust heat exchanger made of durable cast iron, promoting longevity and effective heat transfer. The AWI series boilers feature a modern control system that allows for precise temperature management, enhancing comfort while minimizing energy consumption.

The Crown Boiler AWI295, on the other hand, steps up with a significant heating capacity suited for commercial applications. This model is designed with advanced safety and efficiency technologies, including an intelligent control module that monitors temperature and pressure, ensuring optimal performance while preventing malfunctions. The large water volume design allows for enhanced thermal stability and consistent heating output.

A notable characteristic across these models is their ease of installation and maintenance. Crown Boiler has engineered the units with user-friendly features, including accessible components and simplified diagnostics that help technicians service the boilers swiftly. Moreover, the durability of cast iron construction ensures that these units can withstand high thermal stress while delivering reliable performance over the years.

In summary, Crown Boiler’s AWI061, TWI061, AWI162, AWI128, and AWI295 models offer a range of solutions equipped with advanced technologies and features designed for efficiency and reliability. These boilers are suitable for diverse heating needs, promising optimal comfort and convenience in both residential and commercial settings. With Crown Boiler's longstanding commitment to quality, customers can be assured of a robust heating solution backed by exceptional service.