Crown Boiler AWI162, TWI095, TWI128, TWI061, TWI162, AWI061, AWI195 AWI/TWI Troubleshooting Chart

Models: AWI262 AWI095 TWI095 AWI195 AWI037 TWI162 TWI128 AWI229 AWI295 AWI128 AWI162 TWI061 AWI061

1 42
Download 42 pages 2.92 Kb
Page 32
Image 32

START

AWI/TWI Troubleshooting Chart

Caution: Read page 29 before attempting to use this chart

Thermostat calls for heat

*Pow er off

*Blow n fuse or tripped breaker

*Misw ired or loose electrical connection in 120V line

Remove t'stat or zone valve end sw itch w ires from T&TV terminals on L8148E. Install temporary jumper across terminals T and TV.

Circulator start?

N

N120 volts at L1&L2?

Y

120 volts at

C1&C2?

N

Y24 volts across T&TV?

N

Y

Vent

Y

 

damper

 

 

open?

 

 

 

N

24 volts

 

 

 

 

 

 

 

 

across B and R

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(limit sw itch) in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L8148E ?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120 volts

 

 

 

 

 

 

*Boiler off on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

N

 

 

N

limit

 

 

 

 

across

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminals at

 

 

 

 

 

 

*Defective

 

 

 

 

 

 

circulator?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

high limit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

betw een pins

 

 

 

 

*Seized or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1&4 (blue&yellow )and

 

 

 

 

defective

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2&4 (orange&yellow ) on

 

 

 

 

circulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

damper end of damper

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

harness? See

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 7 on page 29.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does

N

*Defective

circulator

 

 

 

L8148E-see

 

 

 

run now ?

 

 

 

 

 

 

Note 6 on page

 

 

 

 

 

 

 

 

 

 

29.

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Loose connection in t'stat or zone valve end sw itch w iring

*Defective t'stat or zone valve end sw itch

*T'stat or zone system misw ired-consult t'stat or zone valve manufacturer's instructions

*Bad electrical connection betw een C1 or C2 and circulator

Y

*Obstruction in path of damper blade

*Defective damper motor

*Loose connection betw een damper harness and damper

*Loose connection betw een damper harness and L8148E

*Defective damper harness.

*Defective L8148E

32

30

Page 32
Image 32
Crown Boiler AWI162, TWI095, TWI128, TWI061, TWI162, AWI061, AWI195, AWI229, AWI262, AWI037, AWI128 AWI/TWI Troubleshooting Chart