IMPORTANT SAFETY WARNINGS

(SAVE THESE INSTRUCTIONS)

This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.

CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).

CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. There are no user serviceable parts inside except for battery.

CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.

CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the unit.

CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer component.

CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code, ANSI/NFPA 70.

DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical applications. DO NOT use in any circumstance that would affect, operation, safety of any life support equipment or with any medical applications or patient care.

DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation from the aquarium can cause the unit to short out.

INSTALLING YOUR UPS SYSTEM

UNPACKING

Inspect the UPS upon receipt. The box should contain the following:

(1)UPS unit; (1) User’s manual; (1) PowerPanel® Personal Edition software CD; (1) USB device cable; (1) Telephone cable; (1) Warranty registration card; (1) Coaxial Cable

WHAT IS AVR?

The CP685AVR-G / CP825AVR-G provide complete power protection from utility power that is not always consistent. The CP685AVR-G / CP825AVR-G feature 890 Joules / 1030 Joules of surge protection, and provide long lasting battery backup during power outages. The CP685AVR-G / CP825AVR-G ensure consistent power to your computer system and include software that will automatically save your open files and shutdown your computer system during a utility power loss.

AUTOMATIC VOLTAGE REGULATOR

The CP685AVR-G / CP825AVR-G stabilize utility power voltage levels that can be inconsistent. The incoming utility power may be damaging to important data files and hardware, but with Automatic Voltage Regulation, the computer will not experience damaging voltage levels. An Automatic Voltage Regulator automatically increases low or decreases high voltage to a consistent, computer safe 110v/120v. The unit’s powerful battery will provide power only if the incoming voltage drops below 90v or increases above 140v.

BASIC OPERATION

DESCRIPTION

Battery and Surge Protected Outlets

The unit has four battery powered/surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of your equipment during a power failure. ( DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large electrical device into battery and surge protected outlets. The power demands of these devices will overload and possibly damage the unit.)

Full-Time Surge Protection Outlets

The unit has four surge suppression outlets which are always on.

Power Switch

Press the power button to turn the UPS ON or OFF.

Power On Indicator

This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes.

Electrical Wiring Fault Indicator

This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If this is illuminated, it is recommended to disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The unit will not provide surge protection without being plugged into a grounded and properly wired wall outlet.

Communication Protection Ports

Communication protection ports will protect any standard modem, fax, telephone line, network or Ethernet connection (RJ11/RJ45).

Circuit Breaker

Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection.

USB Port and DB-9 Contact Closure Port to PC

The ports allow connection and communication between the USB or DB-9 port on the computer and the UPS unit. The UPS communicates its status to the PowerPanel® Personal Edition software. The DB9 interface is compatible with Power Management provided by Windows® NT/2000/2003/XP and the USB interface is compatible with the Power Management provided by Windows Vista, OS X, and Linux..

Note: Only one of the ports, USB or DB-9, can be used to communicate with your computer at one time.

Note: To install PowerPanel® Personal Edition Software the computer will need MicrosoftR Internet Explore 6.0 or higher installed.

Note: If using the DB-9 port, users need to order the standard RS-232 cable. If you have any questions, email CyberPower

technical support for help. tech@cyberpowersystems.com

Outlets Designed for AC Adapters

The unit has four outlets spaced to allow AC power adapter blocks to be plugged into the UPS without blocking adjacent outlets.

Coax/Cable/DSS Surge Protection

The Coax/Cable/DSS surge protection ports will protect any cable modem, CATV converter, or DSS receiver.

REPLACING THE BATTERY

Replacement of batteries located in an OPERATOR ACCESS AREA.

1.When replacing batteries, replace with the same number of the following battery: BP8-12 / BB for CP685AVR-G; HR1234W / BB for CP825AVR-G.

2.CAUTION! Risk of Energy Hazard, 12 V, maximum 8(BP8-12 for CP685AVR-G) or 9(HR1234W for CP825AVR-G) Ampere-hour battery. Before replacing batteries, remove conductive jewelry such as chains, wrist watches, and rings.

3.CAUTION! Do not dispose of batteries in a fire. The batteries may explode;

4.CAUTION! Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.

CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO LOCAL REGULATIONS.

TO REPLACE THE BATTERY

1.Turn off and unplug all connected equipment.

2.Unplug it from the AC power source.

3.Turn the UPS upside down.

4.Remove the 1 retaining screw.

5.Slide the battery compartment cover completely off of the unit.

6.Remove the battery from the compartment.

7.Disconnect the battery wires from the battery.

8.Install the replacement battery by connecting the red wire and black wire to the positive (+) and negative (-) terminal of the battery.

9.Put the battery back into the compartment.

10.Slide back the battery compartment cover and tighten the retaining screw.

11.Charge the unit for 4 – 8 hours to fully charge the battery.

SYSTEM FUNCTIONAL BLOCK DIAGRAM

Input

EMI Filter

 

Surge

 

 

 

Suppressor

 

 

 

 

AVR

Output

REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sells lead-acid batteries collects used batteries for recycling, as required by local regulations.

TROUBLE SHOOTING

Charger

AC/DC

Normal Mode

Battery Mode

Battery

Inverter

 

Problem

 

Possible Cause

 

Full-time surge protection outlets

 

 

 

stop providing power to

 

Circuit breaker has tripped due to an

 

equipment. Circuit breaker

 

 

 

overload.

 

button is projecting from the side

 

 

 

 

 

of the unit.

 

 

 

 

 

 

 

 

 

Battery not fully charged.

 

The UPS does not perform

 

 

 

 

 

Solution

Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit breaker by depressing the button, and then turn the UPS on.

Recharge the battery by leaving the UPS plugged in.

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT

1.Ensure that the equipment plugged into the outlet does not exceed the UPS unit’s rated capacity (685VA/390W for CP685AVR-G, 825VA/450W for CP825AVR-G). If the rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip.

2.There are many factors that can affect the amount of power that your computer system will require. It is suggested that the load you will be placing on the outlet not exceed 80% of the unit’s capacity.

HARDWARE INSTALLATION GUIDE

1.

Your new UPS may be used immediately upon receipt. However, recharging the

 

battery for at least 8 hours is recommended to ensure that the battery’s maximum

 

charge capacity is achieved. A loss of charge may occur during shipping and

 

storage. To recharge the battery, simply leave the unit plugged into an AC outlet.

2.

With the UPS unit off and unplugged, connect your computer, monitor, and any other

 

peripherals requiring battery backup into the battery power supplied outlets. Plug

 

your other peripheral equipment (printer, scanner, speakers) into the full-time surge protection outlets. DO NOT plug a laser printer, paper

 

shredder, copier, space heater, vacuum, sump pump or other large electrical device into battery and surge protected outlets. The

 

power demands of these devices will overload and possibly damage the unit.

3.

To protect a network connection from surges, connect a network cable into the IN jack of the UPS. Then connect

 

a network cable from the OUT jack on the UPS to the network device.

 

4.

Plug the UPS into a 2 pole, 3 wire grounding receptacle (wall outlet).

Make sure the wall branch outlet is

 

protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air

 

conditioner, refrigerator, copier, etc…). The warranty prohibits the use of extension cords, outlet strips, and surge strips.

5.

Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will “beep”.

6.

If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at

 

least one piece of equipment from the battery power supplied outlets.

Make sure the circuit breaker is depressed and then turn the UPS on.

expected runtime.

Battery is worn out.

 

 

 

 

The on/off switch is designed to

 

prevent damage by rapidly turning it

 

off and on.

 

 

 

The unit is not connected to an AC

The UPS will not turn on.

outlet.

 

 

 

The battery is worn out.

 

 

 

Mechanical problem.

 

 

 

The USB / serial cable is not

 

connected.

 

 

 

The USB / serial cable is connected

PowerPanel® Personal Edition is

to the wrong port.

 

inactive (all icons are gray).

The unit is not providing battery

 

 

power.

 

 

 

The serial cable is not the cable that

 

was included with the UPS unit.

Contact CyberPower Systems about replacement batteries at tech@cyberpowersystems.com

Turn the UPS off. Wait 10 seconds and then turn the UPS on.

The unit must be connected to a 110/120v 60Hz outlet.

Contact CyberPower Systems about replacement batteries at tech@cyberpowersystems.com

Contact CyberPower Systems at tech@cyberpowersystems.com

Connect the USB / serial cable to the UPS unit and an open USB / serial port on the back of the computer. You must use the cable that came with the unit.

Check the back of the computer for an additional USB / serial port. Move the cable to this port.

Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the UPS back on. This should reset the unit.

If you are using a serial cable you must use a CyberPower serial cable. If you need this cable please contact technical support. tech@cyberpowersystems.com

7.

To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.

8.

To store your UPS for an extended period, cover it and store with the battery fully charged. While in storage recharge the battery every three

 

months to ensure battery life.

Additional troubleshooting information can be found at

www.cyberpowersystems.com/support.htm