CPS3000PIE
2.Set-up Mode
Step 1 : The machine enters
Step 2 : By pressing the Display toggle, users can switch between setup functions. User configurable functions are as follows:
a.Delay Time: The time delay between switching from Battery Mode to Line Mode. There are 9 different settings. The default setting is 2.0 minutes.
Function description: The machine will switch from Battery Mode to Line Mode after the AC power transmission reaches stability within the preset delay time.
b.Battery AH: The function adjusts the battery charging current according to the capacity of the connected batteries. It can be configured for 50, 100, 150 and 200AH The default setting is 200AH.
c.Nominal Output Voltage: Configures the correct electricity/voltage supplied in the area/country where the EPS will be used. 220V, 230V and 240V may be selected. The system default setting is 220V.
Function description: AVR Dynamic Voltage Compensation works automatically based on the system voltage settings.
d.Static Frequency Tolerance: There are 6 settings. The default setting is
Function description: The settings may be adjusted to the quality of the electricity in use.
e.Slew Rate: Also called Dynamic Frequency Tolerance. There are 5 different settings. The default value is 4Hz/sec.
Function description: “Slew Rate” indicates the tolerance of a device in accepting frequency variances. The lower “Slew Rate” results in less tolerance but better protection for the connected loads.
f.Battery Shutdown Voltage: This function adjusts the UPS shutdown point according to the battery voltage.
The settable items are sorted by unit as in the following table:
Items | Unit |
Delay Time | Min |
Battery AH | A |
Nominal Output Voltage | V |
Static Frequency Tolerance | % |
Slew Rate | Hz |
Battery Shutdown Voltage | V |