6.Modify the IP, subnet mask or gateway address. Enter the new addresses into the corresponding fields.

7.You will need to enter a User Name and Password for the Remote Management Card in the authentication window, as shown in figure 3. *Default user name: cyber; Default password: cyber.

8.If IP address is successfully, you will see a message that the IP set up is OK, as shown in figure 4.

Figure 3. Authentication window.

Figure 4. Setup IP Address successfully message.

Conformance Approvals

FCC Warning

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does not cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

-Reorient or relocate the receiving antenna.

-Increase the separation between the equipment and receiver.

-Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

-Consult the dealer or an experienced radio/TV technician for help.

This device compiles with Part 15 of the FCC Rules. Operation is subject

Method 2: Using a command prompt

1.Obtain the MAC address from the label on the Remote Management Card. Each Management Card has a unique MAC address.

2.Use the ARP command to set the IP address.

Example:

To assign the IP Address 192.168.10.134 for the Remote Management Card, which has a MAC address of 00-0C-15-0A-0A-0A you will type in the following command prompt from a PC connected to the same network as the Remote Management Card.

(1)Type in “arp-s 192.168.10.134 00-0C-15-0A-0A-0A” then press Enter.

3.Use the Ping command to assign a size of 123 bytes to the IP.

(1)Type in “ping 192.168.10.134 -l 123” then press Enter

(2)If the replies are received, your computer can communicate with the IP address.

WEB INTERFACE Login Account

There are two user account types.

-Administrator (default username: cyber; default password: cyber)

-Viewer (default username: device; default password: cyber)

The administrator can access full functions, including enable/disable the Viewer account, and the viewer can access the read function but can not control or change any setting.

Trouble Shooting

Problem

Solution

Unable to configure

1. Check the LED status , the normal condition

the Remote

is both yellow and green led are on.

Management Card

If green led is off :

by method 1 or

►Check if the Remote Management Card is

method 2

properly seated in the UPS and the UPS

 

power is on.

 

If yellow led is off :

 

►Check if the network connection is valid.

 

2. Check if the operated PC is on the same

 

physical network as Remote Management

 

Card is.

 

 

Unable to ping

1. Use method1 and method2 to get correct IP

the Remote

address of the Remote Management Card.

Management Card

2. If the operated PC is on the different physical

 

network from the Remote Management Card,

 

verify the setting of subnet mask and the IP

 

address of gateway.

 

 

Lost the user name

Please refer to the “Reset to Default Setting /

and password

Recover from a Lost Password

 

part in the user’s manual.

 

 

to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

NOTE: THE MANUFACTURER IS NOT RESPONSIBLE FOR ANY RADIO OR TV INTERFERENCE CAUSED BY UNAUTHORIZED TO THIS EQUIPMENT. SUCH MODIFICATIONS COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.

CyberPower North America

CyberPower Systems (USA), Inc.

Phone: (952)-403-9500 Toll-free: (877)297-6937

4241 12th Avenue E. Suite 400, Shakopee, MN 55379 E-mail: tech@cpsww.com

Website: www.CPSww.com

CyebrPower Europe

CyberPower Systems, Inc.

E-mail: sales@cpsww.eu

Website: www.cpsww.eu

CyberPower Systems France

Z.I. Saint Séverin 28220 CLOYES sur le Loir – France Tél : +33(0)2 37 98 61 50

E-mail : sales@cpsww.com.fr

Page 2
Image 2
CyberPower Systems RMCARD302 manual Conformance Approvals, Trouble Shooting, CyberPower North America, CyebrPower Europe