Planning the Installation

WARNING

IMPORTANT: Observe all governing codes and ordinances during planning and installation. Contact your local building department for further information.

Electrical Requirements

IMPORTANT: The information below applies only to free standing units equipped for use in the U.S.A. and units with the self rimming option.

It is the owner’s responsibility to ensure that the electrical connection of this appliance is performed by a licensed electrician. The electrical installation, including minimum supply wire size and grounding, must be in accordance with the National Electric code ANSI/NFPA 70-1993* (or latest revision) and local codes and ordinances. A copy of this standard may be obtained from:

National Fire Protection Association 1 Batterymarch Park

Quincy, Massachusetts 02269-9101

The correct voltage, frequency and amperage must be supplied to the appliance from a separate, grounded, circuit that is protected by a properly sized circuit breaker or time delay fuse. Refer to the ratings on the range rating label.

ER30D/ER30DSR ELECTRIC CIRCUIT REQUIREMENTS

Circuit Required

Total Connected Load

 

 

240 Vac, 60 Hz, 30 Amps

5.6 kW (23 Amps)

The ratings above are for reference only - refer to the range rating label (see page 3)

Consult local building codes for the type and minimum wire gauge to use for the power requirements listed on the rating label.

Suggested wiring color code: Black, white, red and green.

The wiring needs to be long enough to allow the range to be pulled out from the wall for service, while remaining connected. See page 12 for further details.

The wiring to the range must:

Have a minimum rating of 250 Volts @ 30 Amps

Include a strain relief

Be terminated by tinned leads, closed loop terminals or open ended spade lugs with upturned ends

Where local code permits, a three (3) or four (4) wire appliance cord may be used. The appliance cord must:

Be UL listed type SRD or SRDT

Be equipped with a NEMA 14-50P 4 wire plug or, where local code permits, a NEMA 10-50P 3 wire plug.

NEMA 14-50P Plug

NEMA 10-50P Plug

Prior to range installation, have a licensed electrician install a conduit junction box or electrical receptacle according to the type of wiring used.

Electrical Requirements -

Freestanding Units for Use in Canada

It is the owner’s responsibility to ensure that the required

4 wire electrical outlet is installed by a licensed electrician as specified below prior to range installation. The electrical outlet installation, including minimum supply wire size and grounding, must be in accordance with all governing codes and ordinances.

The correct voltage, frequency and amperage must be supplied to the appliance from a separate, grounded, circuit that is protected by a properly sized circuit breaker or time delay fuse. Refer to the ratings on the range rating label.

ER30D-C ELECTRIC CIRCUIT REQUIREMENTS

Circuit Required

Total Connected Load

 

 

240 Vac, 60 Hz, 30 Amps

5.6 kW (23 Amps)

 

 

The ratings above are for reference only - refer to the range rating label (see page 3)

Freestanding ranges equipped for use in Canada come pre- wired with a 4 wire appliance cord and NEMA 14-50P plug.

Do not modify the factory wiring. The plug is designed to plug directly into a NEMA 14-50R electrical receptacle installed by a licensed electrician according to the above specifications.

NEMA 14-50R Receptacle

Gas Supply Requirements

Check your local building codes for the proper method of installation. In the absence of local codes, this appliance should be installed in accordance with the National Fuel Gas Code ANSI Z223.1.

Be certain that the appliance being installed is correct for the gas service provided (natural gas or LP gas). Also, if operating the range at an altitude above 4000 ft. (1219 m) make sure it is equipped for high altitude operation. Refer to the range rating label and the table on page 3 to determine the correct model.

See the table below for gas supply pressure requirements.

The regulator inlet accommodates a 3/4” gas line. The range ships with a 1/2” to 3/4” adapter connected to the regulator.

GAS SUPPLY PRESSURE REQUIREMENTS

Gas Type

Manifold Pressure

Minimum Gas

Supply Pressure

 

 

Natural Gas

5” Water Column

6” Water Column

Propane (LP)

10” Water Column

11” Water Column

The ratings above are for reference only - refer to the range rating label (see page 3)