SpecialData3

Specify 0 for DF1 with Full Duplex and BCC

 

Specify 1 for DF1 with Half Duplex and CRC

 

 

SpecialData4

When using a 1770-KFC15 gateway device, use this

 

Extra Hop parameter to access the ControlNet address

 

of the CNB module. The DeltaV PSIC device address

 

must be between 1-50. This parameter has only the

 

following values:

 

1. 100 for ControlNet node in slot 0.

 

2. 150 for ControlNet node in slot 1.

 

3. 200 for ControlNet node in slot 2.

 

All other values will generate an error message. Please

 

refer to Allen Bradley 1747-KFC15 and 1770-KFC15,

 

Firmware Version 4.2 release notes for more detailed

 

ControlNet information.

 

 

4.2Device And Dataset Configuration

The following paragraphs discuss some attributes in the device and Dataset configuration:

4.2.1Device Address:

The device address attribute is located in the device configuration box under port. It is the PLC/SLC node address, not the 1785-KE or 1770-KF2 communication module address. This number is used by DeltaV to uniquely identify each PLC in the Data Highway Plus network. The PLC node address is an octal-based number set with dip switches on the PLC. Therefore, it needs to be converted to a decimal number in the serial card configuration. For example, an octal address of 10 on the PLC corresponds to a decimal address of 8 in the serial card. The acceptable address range is between 1 and 255.

4.2.2Output Mode:

Two output modes are available in the driver: block output (0) and single output (1). In typed or ranged transaction (DeviceDataType 4,5,8, and 9), the block output mode writes the entire data block for every output data value change. Therefore, it is undesirable to contain any foreign-device-controlled (device other than DeltaV) values within the block. For example, if a PLC-5 memory N7:5 is written by a PLC-2, and user defines a Dataset with a range of N7:0 to N7:10 in block output mode, an output operation will overwrite the N7:5 with the value in the DeltaV database.

Single output mode allows individual value to be sent out, leaving other values in the Dataset unaffected. In the binary file type, word value is treated as a single value. It does not allow user to write a specific bit within a word. Therefore, the entire 16 bit will be written when a single discrete output value changes. When communication with a PLC-5, writing single bit values in a multi-bit Dataset can be achieved with Read-Modify-Write (RMW) transaction (DeviceDataType 7 and 10). The RMW is used only with binary file type and single output mode. Each bit can be set or reset within a binary file without