4.4Serial Port Configuration for DeltaV PSIC

In order for proper communication between the Programmable Serial Interface Card and the Allen-Bradley PLC, the serial port settings on both devices must be configured properly.

The PSIC serial port can be configured via a combination of the following settings through the DeltaV Explorer Menu using the Properties box.

￿￿

Protocol Type

Custom

￿￿

Mode

Master

￿￿

Retry Count

0 to 255

￿￿

Message time-out

100 to 25500ms

￿￿

Transmit Delay

0 to 25500ms

￿￿ Send Outputs on Startup

Yes or No

￿￿

Port Type

RS-232, RS-422/485 Half - Duplex, RS -

 

 

422/485 Full - Duplex

￿￿

Baud Rate

300, 1200, 2400, 4800, 9600, 38400

 

 

57600, 115200

￿￿

Parity

None, Even or Odd

￿￿

Data Bits

7or 8