Product Overview

1 Phase CliQ DIN Rail Power Supply 3 Phase CliQ DIN Rail Power Supply

Output (DC)
Output power 60 W 60 W 120 W 240 W 480 W 60 W 120 W 240 W 480 W
Output voltage range 22 V - 28 V 22 V - 28 V 22 V - 28 V 22 V - 28 V 22 V - 28 V 22 V - 28 V 22 V - 28 V 22 V - 28 V 22 V - 28 V
Output current 2.5 A 2.5 A 5 A 10 A 20 A 2.5 A 5 A 10 A 20 A
Residual ripple/peak switching
(20 MHz) (at nominal values)
< 50 mV / < 240 mVpp < 50 mV / < 240 mVpp < 50 mV / < 240 mVpp < 50 mV / < 240 mVpp < 50 mV / < 240 mVpp < 50 mV / < 240 mVpp < 50 mV / < 240 mVpp < 50 mV / < 240 mVpp < 50 mV / < 240 mVpp
Mains buffering at nominal load (typ.) > 20 ms @ 115 Vac,
> 125 ms @ 230 Vac
> 20 ms @ 115 Vac,
> 125 ms @ 230 Vac
> 35 ms @ 115 Vac,
> 70 ms @ 230 Vac
> 20 ms @ 115 Vac & 230 Vac > 20 ms @ 115 Vac & 230 Vac > 30 ms @ 3 x 400 Vac,
> 60 ms @ 3 x 500 Vac
> 35 ms @ 3 x 400 Vac,
> 70 ms @ 3 x 500 Vac
> 35 ms @ 3 x 400 Vac,
> 60 ms @ 3 x 500 Vac
> 20 ms @ 3 x 400 Vac,
> 40 ms @ 3 x 500 Vac
Line regulation < 0.5% typ. (@ 85 - 264 Vac input,
100% load)
< 0.5% typ. (@ 85 - 264 Vac input,
100% load)
< 0.5% typ. (@ 85 - 264 Vac input,
100% load)
< 0.5% typ. (@ 85 - 264 Vac input,
100% load)
< 0.5% typ. (@ 85 - 264 Vac input,
100% load)
< 0.5% typ. (@ 320 - 575 Vac input,
100% load)
< 0.5% typ. (@ 320 - 575 Vac input,
100% load)
< 0.5% typ. (@ 320 - 575 Vac input,
100% load)
< 0.5% typ. (@ 320 - 575 Vac input,
100% load)
Load regulation < 1% typ.
(with rated input, 0 - 100% load)
< 1% typ.
(with rated input, 0 - 100% load)
< 1% typ.
(with rated input, 0 - 100% load)
< 1% typ.
(with rated input, 0 - 100% load)
< 1% typ.
(with rated input, 0 - 100% load)
< 1% typ.
(with rated input, 0 - 100% load)
< 1% typ.
(with rated input, 0 - 100% load)
< 1% typ. (with rated input, 0 - 100%
load)
< 1% typ. (with rated input, 0 - 100%
load)
Input (AC)
Input voltage range 85 - 264 Vac
(DC input range 120 - 375 Vdc)
85 - 264 Vac
(DC input range 120 - 375 Vdc)
85 - 264 Vac
(DC input range 120 - 375 Vdc)
85 - 264 Vac
(DC input range 120 - 375 Vdc)
85 - 264 Vac
(DC input range 120 - 375 Vdc)
320 - 575 Vac
(DC input range 450 - 800 Vdc)
320 - 575 Vac
(DC input range 450 - 800 Vdc)
320 - 575 Vac
(DC input range 450 - 800 Vdc)
320 - 575 Vac
(DC input range 450 - 800 Vdc)
Input frequency 47 Hz - 63 Hz 47 Hz - 63 Hz 47 Hz - 63 Hz 47 Hz - 63 Hz 47 Hz - 63 Hz 47 Hz - 63 Hz 47 Hz - 63 Hz 47 Hz - 63 Hz 47 Hz - 63 Hz
Nominal current 1.1 A @ 115 Vac, 0.7 A @ 230 Vac 1.1 A @ 115 Vac, 0.7 A @ 230 Vac 1.4 A @ 115 Vac, 0.8 A @ 230 Vac 2.9 A @ 115 Vac, 1.5 A @ 230 Vac 5.7 A @ 115 Vac, 2.8 A @ 230 Vac 0.3 A @ 400 Vac approx. 0.5 A @ 400 Vac approx. 0.8 A @ 400 Vac approx. 1.6 A @ 400 Vac approx.
Efciency > 85% typ. > 85% typ. > 84% typ. > 84% typ. > 86% typ. > 86% @ 3 x 400 Vac,
> 85% @ 3 x 500 Vac
> 86% @ 3 x 400 Vac,
> 85% @ 3 x 500 Vac
> 87% @ 3 x 400 Vac,
> 86% @ 3 x 500 Vac
> 87% @ 3 x 400 Vac,
> 86% @ 3 x 500 Vac
Power factor Conform to EN 61000-3-2 STD Conform to EN 61000-3-2 STD Conform to EN 61000-3-2 STD Conform to EN 61000-3-2 STD Conform to EN 61000-3-2 STD Conform to EN 61000-3-2 STD Conform to EN 61000-3-2 STD Conform to EN 61000-3-2 STD Conform to EN 61000-3-2 STD
Inrush current limitation I²t (+25°C) typ. 30 A @ 115 Vac,
60 A @ 230 Vac
30 A @ 115 Vac,
60 A @ 230 Vac
< 80 A @ 115 Vac No damage at I²t ratings for all I/P de-
vices shall not exceed their rating
No damage at I²t ratings for all I/P
devices shall not exceed their rating
< 30 A @ 400 Vac < 30 A @ 400 Vac < 40 A @ 400 Vac < 50 A @ 400 Vac
Leakage current < 1 mA < 1 mA < 1 mA < 3.5 mA < 1 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA
Mechanical design
Case cover Plastic (PC) Aluminium (AI5052) Aluminium (AI5052) Aluminium (AI5052) Aluminium (AI5052) Aluminium (AI5052) Aluminium (AI5052) Aluminium (AI5052) Aluminium (AI5052)
Dimensions (L x W x H) 126 mm x 32 mm x 113 mm 121 mm x 32 mm x 120 mm 121 mm x 50 mm x 115 mm 121 mm x 85 mm x 118.5 mm 121 mm x 160 mm x 115 mm 121 mm x 70 mm x 118.5 mm 121 mm x 70 mm x 118.5 mm 121 mm x 85 mm x 120.5 mm 121 mm x 160 mm x 115 mm
Unit weight / box 0.325 kg 0.370 kg 0.540 kg 1.040 kg 1.800 kg 0.560 kg 0.720 kg 0.990 kg 1.710 kg
MTBF > 800,000 hrs > 800,000 hrs > 800,000 hrs > 300,000 hrs > 300,000 hrs > 500,000 hrs > 500,000 hrs > 300,000 hrs > 300,000 hrs
Noise Sound pressure level (SPL) < 40 dBA Sound pressure level (SPL) < 40 dBA Sound pressure level (SPL) < 40 dBA Sound pressure level (SPL) < 40 dBA Sound pressure level (SPL) < 40 dBA Sound pressure level (SPL) < 40 dBA Sound pressure level (SPL) < 40 dBA Sound pressure level (SPL) < 40 dBA Sound pressure level (SPL) < 40 dBA
Cooling Convection Convection Convection Convection Convection Convection Convection Convection Convection
Input terminal M4 x 3 M4 x 3 M4 x 3 M4 x 3 M4 x 3 M4 x 4; 600 V rating M4 x 4; 600 V rating M4 x 4; 600 V rating M4 x 4; 600 V rating
Output terminal M4 x 2 M4 x 2 M4 x 2 (2 pcs.) M4 x 2 (2 pcs.) M4 x 2 (2 pcs.) M4 x 2 (2 pcs); 600 V rating M4 x 2 (2 pcs); 600 V rating M4 x 2 (2 pcs); 600 V rating M4 x 2 (2 pcs); 600 V rating
Mounting rail Standard TS35 mounting rail Standard TS35 mounting rail Standard TS35 mounting rail Standard TS35 mounting rail Standard TS35 mounting rail Standard TS35 mounting rail Standard TS35 mounting rail Standard TS35 mounting rail Standard TS35 mounting rail
Shock proof IEC 60068-2-27 IEC 60068-2-27 IEC 60068-2-27 IEC 60068-2-27 IEC 60068-2-27 IEC 60068-2-27 IEC 60068-2-27 IEC 60068-2-27 IEC 60068-2-27
Vibration IEC 60068-2-6 IEC 60068-2-6 IEC 60068-2-6 IEC 60068-2-6 IEC 60068-2-6 IEC 60068-2-6 IEC 60068-2-6 IEC 60068-2-6 IEC 60068-2-6
Protection structure EN 60950 meet IPX0 EN 60950 meet IPX0 EN 60950 meet IPX0 EN 60950 meet IPX0 EN 60950 meet IPX0 EN 60950 meet IPX0 EN 60950 meet IPX0 EN 60950 meet IPX0 EN 60950 meet IPX0
Safety / Environmental
EMC / Emissions Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Class B / EN55022, CISPR22, Class B;
FCC Tilte 47; EN 61204-3
(Class B on AC & Class A on DC side)
Immunity EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC 61000-4-
5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or IEEE
C62.41; EN 61000-3-2, 1994
EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC 61000-
4-5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or
IEEE C62.41; EN 61000-3-2, 1994
EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC 61000-
4-5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or
IEEE C62.41; EN 61000-3-2, 1994
EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC 61000-
4-5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or
IEEE C62.41; EN 61000-3-2, 1994
EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC
61000-4-5, 1995; EN 61000-4-6,
1996; EN 61000-4-8 or IEC 61000-
4-12 or IEEE C62.41; EN 61000-3-2,
1994
EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC 61000-
4-5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or
IEEE C62.41; EN 61000-3-2, 1994
EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC 61000-
4-5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or
IEEE C62.41; EN 61000-3-2, 1994
EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC 61000-
4-5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or
IEEE C62.41; EN 61000-3-2, 1994
EN 61000-4-2, 1995; EN 61000-4-3,
1998; EN 61000-4-4, 1995; IEC 61000-4-
5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or IEEE
C62.41; EN 61000-3-2, 1994
Approvals UL508, EN 60950, cULus 60950,
EN 50178, EN 60204, GS, CCSAus to
CSA C22.2 No. 60950-1: 03
UL508, EN 60950, cULus 60950,
EN 50178, EN 60204, GS
UL508, EN 60950, cULus 60950,
EN 50178, EN 60204, GS
UL508, EN 60950, cULus 60950, EN
50178, EN 60204, GS
UL508, EN 60950, cULus 60950, EN
50178, EN 60204, GS
UL508, EN 60950, cULus 60950, EN
50178, EN 60204, GS
UL508, EN 60950, cULus 60950, EN
50178, EN 60204, GS
UL508, EN 60950, cULus 60950, EN
50178, EN 60204, GS
UL508, EN 60950, cULus 60950, EN
50178, EN 60204, GS
Voltage dips Conform to EN 61000-4-11 Conform to EN 61000-4-11 Conform to EN 61000-4-11 Conform to EN 61000-4-11 Conform to EN 61000-4-11 Conform to EN 61000-4-11 Conform to EN 61000-4-11 Conform to EN 61000-4-11 Conform to EN 61000-4-11
Galvanic isolation Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac
Operating ambient temperature -20 °C ~ 75 °C * -20 °C ~ 75 °C * -20 °C ~ 75 °C * -20 °C ~ 75 °C * -20 °C ~ 75 °C * -20 °C ~ 75 °C * -20 °C ~ 75 °C * -20 °C ~ 75 °C * -20 °C ~ 75 °C *
Storage temperature -25 °C ~ 85 °C -25 °C ~ 85 °C -25 °C ~ 85 °C -25 °C ~ 85 °C -25 °C ~ 85 °C -25 °C ~ 85 °C -25 °C ~ 85 °C -25 °C ~ 85 °C -25 °C ~ 85 °C
Humidity operation < 95 % < 95 % < 95 % < 95 % < 95 % < 95 % < 95 % < 95 % < 95 %
Note (*) * Operating amb. < 0°C until -20°C
derate power by 1% / °C; Operating
amb. > 50°C derate power by 2.5% / C;
Operating amb. > 70°C derate power
by 4% / °C
* Operating amb. < 0°C until -20°C
derate power by 1% / °C; Operating
amb. > 50°C derate power by 2.5% / °C
* Operating amb. > 50°C derate power
by 2.5% / °C
* Operating amb. > 50°C derate power
by 2.5% / °C; Operating amb. > 70°C
derate power by 4% / °C
* Operating amb. > 50°C derate
power by 2.5% / °C
* Operating amb. > 50°C derate power
by 2.5% / °C
* Operating amb. > 50°C derate power
by 2.5% / °C
* Operating amb. > 50°C derate power
by 2.5% / °C; Operating amb. > 70°C
derate power by 4% / °C
* Operating amb. > 50°C derate power
by 2.5% / °C
DRP024V060W1AZ DRP024V060W1AA DRP024V120W1AA DRP024V240W1AA DRP024V480W1AA DRP024V060W3AA DRP024V120W3AA DRP024V240W3AA DRP024V480W3AA