Switch Mode Power SupplyDRP024V060W1BA

Technical Data

 

60W1Ph

 

Input Data (1)

 

 

 

 

Nominal input voltage and frequency

 

 

100-240VAC / 50-60Hz

 

Voltage range

 

 

85-264VAC (120 – 375 VDC)

 

Frequency Range

 

 

47-63Hz

 

Nominal current

 

 

1.5A max @115VAC, 1.0A max @230VAC

 

Inrush current limitation. I2t (+25°C) typ.

 

 

< 35A @ 230VAC

 

Mains buffering at nominal load (typ.)

 

 

> 20ms @ 115VAC, > 125ms @ 230VAC

 

Turn-on time

 

 

< 3.0sec.

 

Internal fuse

 

 

T 3.15 AH / 250V

 

Recommended backup fuse: Power circuit-breaker characteristic

 

 

6A, 10A or 16A : B

 

Leakage current

 

 

< 1mA

 

Energy Star Level

 

 

V

 

 

 

 

 

 

Output Data (2)

 

 

 

 

Nominal output voltage UN / tolerance

 

 

24VDC±2%

 

Setting range of the output voltage

 

 

24-28VDC

 

Nominal current

 

 

2.5A

 

De-rating above +50°C

 

 

> 50°C (2.5% / °C)

 

Startup with capacitive loads

 

 

Max 8,000µF at 25°C

 

Max. power dissipation idling / nominal load approx.

 

 

7.4W

 

Efficiency

 

 

> 89% typical.

 

Residual ripple / peak switching (20 MHz) (at nominal values)

 

 

< 50mV / < 150mVpp.

 

Can be connected in parallel for redundancy and increased capacity

 

 

YES with ORing Diode or Redundancy module

 

Surge voltage protection against internal surge voltages

 

 

YES

 

 

 

 

 

 

Certification/Standards

 

 

 

 

Electrical equipment of machines

 

 

IEC60204-1 (overvoltage category III)

 

Safety transformers for switched-mode power supply units

 

 

 

 

 

 

 

TUV BAUART to EN60950-1, UL/C-UL recognized to

 

Electrical safety (of information technology equipment)

 

 

UL60950-1, CSA C22.2 No. 60950-1,

 

 

 

 

CB scheme to IEC60950-1

 

Industrial Control Equipment

 

 

UL / C-UL Listed UL508 and CSA C22.2 No. 107.1-01, CSA to

 

 

 

CSA C22.2 No.107.1-01 (file no. 181564)

 

 

 

 

 

Electronic equipment for use in electrical power Installations

 

 

EN50178 / IEC62103

 

Safety entry low voltage

 

 

PELV (EN60204), SELV (EN60950)

 

Safe isolation

 

 

DIN.VDE 0100-410

 

Protection against electric shock

 

 

DIN 57100-410

 

Protection against shock currents, basic requirements for protective

 

 

VDE 0106-101

 

separation in electrical equipment

 

 

 

 

Limitation of mains harmonic currents

 

 

DIN57100-410

2/13

Rev: 00,

1/10/2011

 

Page 2
Image 2
Delta Electronics DRP024V060W1BA warranty Technical Data