Delta Electronics DTC2000 Series LED Display, Password Function, RS-485 Communication, y RTU Mode

Models: DTC1000 Series DTC2000 Series

1 2
Download 2 pages 18.33 Kb
Page 2
Image 2
LED Display

Mode

Alarm Type

 

Alarm Output Operation

2

Alarm output will be enabled when the temperature reaches the upper limit.

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV exceeds SV + AL-H.

 

 

 

 

 

SV

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Alarm output will be enabled when the temperature reaches the lower limit.

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV falls below SV – AL-L.

 

 

AL-L

SV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

y Alarm will be enabled when the PV is between SV + AL-L and SV – AL-L.

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

SV

AL-H

 

 

 

 

 

 

 

AL-L

 

Alarm output will be enabled when the temperature reaches the absolute

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

value of the upper and lower limits.

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV exceeds AL-H or falls below AL-L.

 

 

 

 

 

AL-L

 

 

AL-H

 

Alarm output will be enabled when the temperature reaches the absolute

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

6

value of the upper limit.

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV exceeds AL-H.

 

 

 

 

 

 

 

 

 

 

AL-H

 

Alarm output will be enabled when the temperature reaches the absolute

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

value of the lower limit.

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV falls below AL-L.

 

 

 

 

 

AL-L

 

 

 

 

 

8

Standby upper/lower limit alarm

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H or

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

falls below SV – AL-L.

 

 

 

 

 

AL-L

SV

AL-H

9

Upper limit standby alarm

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H.

 

 

 

SV

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Lower limit standby alarm

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV reaches SV and falls below SV – AL-L

 

 

 

SV

 

 

 

 

 

 

 

 

 

AL-L

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Upper limit hysteresis alarm

 

ON

 

 

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV exceeds SV + AL-H and disabled when

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the PV falls below SV + AL-L.

 

 

 

 

 

 

 

 

AL-L

AL-H

12

Lower limit hysteresis alarm

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

y Alarm will be enabled when the PV falls below SV – AL-H and disabled

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when the PV exceeds SV – AL-L.

 

 

 

 

 

AL-H

AL-L

 

 

 

Note: AL-H and AL-L include AL1H, AL2H, AL1L and AL2L. When Output 1 is set to Alarm Output, use AL1H (1024H) and AL1L (1025H). When Output 2 is set to Alarm Output, use AL2H (1026H) and AL2L (1027H).

LED Display

1.When power is normal, POWER LED will be on.

2.After DTC1000/2000 is switched on, all LED will be on. The communication protocol will be displayed in 1 second, followed by the communication address in the next second.

3.RUN LED is on when the control is executing.

4.ERROR LED is on when errors occur in input, memory or communication.

5.When an output is executing, its corresponding output LED will be on.

6.AT LED flashes when PID parameters are being auto-tuned.

7.RX LED flashes when DTC1000/2000 receives communication signals. TX LED flashes when DTC1000/2000 sends out communication signals.

Communication protocol displayed on LED after the power of DTC1000/2000 is switched on:

AT

 

TX

 

RX

 

O1

O2

 

Err

 

Run

000: 2,400bps

001: 4,800bps

010: 9,600bps

 

Parity 00: None

01: Even

 

0: ASCII

 

0:2 Stop bits

011: 19,200bps 100: 38,400bps

 

 

 

10: Odd

 

 

1: RTU

 

1:1 Stop bit

 

 

 

 

 

 

 

 

 

 

 

 

Communication address display: AT (bit 6) and Run (bit 0) are combined to binary code.

Password Function

The default setting of the password is disabled. To enable the password function, enter the 4-character password in the specific communication address. The password is protected by 3 levels.

1.Level 1: Only LED status, SV and PV can be read. No settings can be modified.

2.Level 2: Only LED status, SV and PV can be read. Only SV can be modified.

3.Level 3: All SV can be read. Only SV and auto-tuning can be modified.

4.Level 4: No password protection.

When a password is set (in 106EH ~ 1070H), the protection will enter Level 1. To enter other levels, enter the corresponding password (in 106BH ~ 106DH). After DTC1000/2000 is switched off, the protection will return to Level 1. To unlock the password protection, the user has to remove all the passwords (in 106EH ~ 1070H).

The password protection level can be read in 106EH ~ 1070H:

bit

b0

 

b1

 

b2

 

b3

 

b4

 

b5

b6

Status

Level 1

 

Level 2

 

Level 3

 

Level 1 locked

 

Level 2 locked

 

Level 3 locked

Unlocked

 

 

 

 

 

 

 

 

 

 

 

 

 

bit = 0 refers to no password is set. bit = 1 refers to the password has been set (b0 ~ b2). b3 ~ b6 display the current level status.

Synchronous Communication Protocol & Auto ID Setup

This function allows the user to set the communication protocol of DTC2000 to the same protocol as set in the first DTC1000. The station IDs of DTC1000/2000 are arranged in decreasing order. Follow the steps below.

1.Set the auto communication ID of DTC1000 to “1” (communication address: 1022H).

2.Switch off DTC1000 before connecting it to DTC2000. Switch it on again.

3.Default communication protocol: 9,600bps, 7 bits, Even, 1 stop bit, communication address 01.

4.This function will consume 3 ~ 5 seconds more when you switch on your DTC.

RS-485 Communication

1.Supports transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps;

2.Does not support 7, N, 1 / 8, E, 2 / 8, O, 2 communication format;

3.Communication protocol: Modbus ASCII/RTU;

4.Function code: 03H (read Max. 8 words in register), 06H (write 1 word into register), 01H (read Max. 16 bits of data), 05H (write 1 bit into register).

Address

 

Setting

 

Content

Explanation

 

 

 

 

 

Unit: 0.1 degree. Analog input: 1EU.

 

 

 

 

 

The read values below indicate the occurrence of errors:

 

 

 

 

 

8002H: Temperature not acquired yet

1000H

 

 

 

Present temperature value (PV)

8003H: Temperature sensor not connected

 

 

 

 

 

8004H: Incorrect sensor type

 

 

 

 

 

8006H: Unable to acquire temperature, ADC input error

 

 

 

 

 

8007H: Unable to read/write the memory

1001H

 

0

 

Set point (SV)

Unit: 0.1 degree. Analog input: 1EU.

1002H

 

6,000

 

Upper-limit of temperature range

The content shall not be bigger than the range. Unit: 0.1°

1003H

 

-200

 

Lower-limit of temperature range

The content shall not be smaller than the range. Unit: 0.1°

1004H

 

12

 

Input sensor type

See the table in “Input” section.

1005H

 

0

 

Control method

0: PID, 1: ON/OFF, 2: Manual, 3: programmable PID

1007H

 

4

 

Control cycle of Output 1

0 ~ 99, 0: 0.5sec

1008H

 

4

 

Control cycle of Output 2

0 ~ 99, 0: 0.5sec (Invalid when the 2 outputs are the same

 

 

control.)

 

 

 

 

 

1009H

 

476

 

Proportional band value

1 ~ 9,999, Unit: 0.1°. Analog input: 1EU

100AH

 

260

 

Ti value

0 ~ 9,999

100BH

 

41

 

Td value

0 ~ 9,999

100CH

 

0

 

Default integration value

0 ~ 1,000, Unit: 0.1%

100DH

 

0

 

Offset compensation value for proportional

0 ~ 1,000, Unit: 0.1%

 

 

control (when Ti=0))

 

 

 

 

 

100EH

 

100

 

COEF setting when in dual control output

1 ~ 9,999, Unit: 0.01

100FH

 

0

 

Deadband setting when in dual control

-999 ~ 9,999, Unit: 0.1° or 1EU

 

 

output

 

 

 

 

 

1010H

 

0

 

Hysteresis of Output 1

0 ~ 9,999, Unit: 0.1° or 1EU

1011H

 

0

 

Hysteresis of Output 2

0 ~ 9,999, Unit: 0.1° or 1EU

1012H

 

0

 

Read/write output percentage of Output 1

Unit: 0.1%. “Write” is only applicable in manual mode.

1013H

 

0

 

Read/write output percentage of Output 2

Unit: 0.1%. “Write” is only applicable in manual mode.

1014H

 

0

 

Upper-limit regulation for analog linear output

1 scale = 2.8μA = 1.3mV

1015H

 

0

 

Lower-limit regulation for analog linear output

1 scale = 2.8μA = 1.3mV

1016H

 

0

 

Temperature offset regulation value

-999 ~ +999, Unit: 0.1° or 1EU

1020H

 

0

 

Output mode for Alarm 1

See “Alarm Output” section.

1021H

 

0

 

Output mode for Alarm 2

See “Alarm Output” section.

1022H

 

0

 

Communication flag auto-set

0: Communication banned, 1: Communication auto-set

1024H

 

40

 

Upper limit for Alarm 1

See “Alarm Output” section.

1025H

 

40

 

Lower limit for Alarm 1

See “Alarm Output” section.

1026H

 

40

 

Upper limit for Alarm 2

See “Alarm Output” section.

1027H

 

40

 

Lower limit for Alarm 2

See “Alarm Output” section.

102AH

 

 

 

Read/write status

b1: ALM2, b2: °C, b3: °F, b4: ALM1, b5: O2, b6:O1, b7: AT

102CH

 

0

 

Positive/negative proportional output

0: positive, 1: negative

102EH

 

 

 

LED status

b0: RUN, b1: ERR, b2: O2, b3: O1, b4: RX, b5:TX b6: AT

102FH

 

 

 

Software version

V1.00 is indicated as 0x100

1030H

 

0

 

No. of start pattern

0 ~ 7

1032H

 

 

 

Remaining time of the executed step

Unit: second

1033H

 

 

 

Remaining time of the executed step

Unit: minute

1034H

 

 

 

No. of currently executed step

0 ~ 7

1035H

 

 

 

No. of currently executed pattern

0 ~ 7

1037H

 

1,000

 

Upper limit of proportional output

0 ~ 100% upper limit of analog output, Unit: 0.1%

1038H

 

0

 

Lower limit of proportional output

0 ~ 100% lower limit of analog output, Unit: 0.1%

1040H~

 

7

 

Number of steps in a pattern

0 ~ 7 = N refers to the pattern will be executed from Step 0

1043H

 

 

to Step N.

 

 

 

 

1050H~

 

0

 

Additional number of cycles for a pattern

0 ~ 199 refers to the pattern will be executed for 1 ~ 200

1053H

 

 

times.

 

 

 

 

1060H~

 

0

 

No. of the link pattern for the current

0 ~ 8, 8 refers to end of the program. 0 ~ 7 refers to the

1063H

 

 

pattern

next pattern No. following the current pattern.

 

 

 

1068H

 

1

 

Run/Stop setting

0: Stop, 1: Run, 2: Program end, 3: Program hold

1069H

 

0

 

Control selection of Output 1

0: Heating, 1: Cooling, 2: Alarm, 3: Proportional output

106AH

 

0

 

Control selection of Output 2

0: Heating, 1: Cooling, 2: Alarm

106BH

 

0

 

Unlock Level 1 password protection.

Shall be the same as Level 1 password (106E)

 

 

Read/write allowed

 

 

 

 

 

106CH

 

0

 

Unlock Level 2 password protection. Use

Shall be the same as Level 2 password (106F)

 

 

Level 3.

 

 

 

 

 

106DH

 

0

 

Unlock Level 3 password protection. Use

Shall be the same as Level 3 password (1070)

 

 

Level 2

 

 

 

 

 

106EH

 

0

 

Unlock Level 1 password protection/Set up

Unlock password before setting it up.

 

 

password

 

 

 

 

 

106FH

 

0

 

Unlock Level 2 password protection/Set up

Unlock password before setting it up.

 

 

password

 

 

 

 

 

1070H

 

0

 

Unlock Level 3 password protection/Set up

Unlock password before setting it up.

 

 

password

 

 

 

 

 

1071H

 

1

 

Read/write communication address

1 ~ 247

1072H

 

0

 

Read/write communication format

1: RTU, 0: ASCII

1073H

 

2

 

Read/write communication speed

0 ~ 4: 2,400 ~ 38,400

1074H

 

1

 

Read/write communication data length

0: 8 bits, 1: 7 bits

1075H

 

1

 

Read/write parity bit

0: None, 1: Even, 2: Odd

1076H

 

1

 

Read/write stop bit

0: 2 stop bits, 1: 1 stop bit

2000H~

 

0

 

SV temperature for Pattern 0 ~ 7.

Unit: 0.1°

203FH

 

 

SV for Pattern 0 is set in 2000H ~ 2007H

 

 

 

 

2080H~

 

0

 

Execution time for Pattern 0~7.

0 ~ 900 (1 scale = 1 minute)

20BFH

 

 

Time for Pattern 0 is set in 2080H ~ 2087H

 

 

 

 

5.

Address and content of the bit register (read bits are stored starting from LSB, and written data is FF00H, set the

 

bit as 1. 0000H sets the bits data to “0”).

 

 

0811H

Temperature unit display

0:°F, 1: °C (Default)

 

0813H

Read/write auto-tuning status

0: End (Default), 1: Start

 

0814H

Run/Stop setting

0: Stop, 1: Run (Default)

 

0815H

Program hold flag

1: Program hold

 

0816H

Program stop flag

1: Program stop

 

 

 

 

6.

Communication format: Command 01: read bit, 05: write bit, 03: read word, 06: write word.

y ASCII Mode

Read Command

 

 

 

Read Response Message

 

 

Write Command

 

 

 

Write Response Message

 

Start word

’:’

’:’

 

Start word

’:’

’:’

 

Start word

’:’

’:’

 

Start word

’:’

’:’

Machine address 1

‘0’

‘0’

 

Machine address 1

‘0’

‘0’

 

Machine address 1

‘0’

‘0’

 

Machine address 1

‘0’

‘0’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Machine address 0

‘1’

‘1’

 

Machine address 0

‘1’

‘1’

 

Machine address 0

‘1’

‘1’

 

Machine address 0

‘1’

‘1’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command 1

‘0’

‘0’

 

Command 1

‘0’

‘0’

 

Command 1

‘0’

‘0’

 

Command 1

‘0’

‘0’

Command 0

‘3’

‘1’

 

Command 0

‘3’

‘1’

 

Command 0

‘6’

‘5’

 

Command 0

‘6’

‘5’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘1’

‘0’

 

Length of response data

‘0’

‘0’

 

 

‘1’

‘0’

 

 

‘1’

‘0’

Read staring address of

‘0’

‘8’

 

(byte)

‘4’

‘2’

 

Write data address

‘0’

‘8’

 

Write data address

‘0’

‘8’

 

 

 

 

data/bit

‘0’

‘1’

 

 

‘0’

‘1’

 

‘0’

‘1’

 

‘0’

‘1’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘0’

‘0’

 

Data content in

‘1’

‘7’

 

 

‘1’

‘0’

 

 

‘1’

‘0’

 

‘0’

‘0’

 

1000H/081xH

‘F’

‘0’

 

 

‘0’

‘F’

 

 

‘0’

‘F’

 

 

 

 

 

 

 

Read length of data/bit

‘0’

‘0’

 

 

‘4’

‘1’

 

To write data content

‘3’

‘F’

 

Write data content

‘3’

‘F’

(word/bit)

‘0’

‘0’

 

 

‘0’

 

 

‘E’

‘0’

 

‘E’

‘0’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘2’

‘9’

 

Data content in 1001H

‘0’

 

 

 

‘8’

‘0’

 

 

‘8’

‘0’

LRC1 check

‘E’

‘D’

 

‘0’

 

 

LRC1

‘F’

‘E’

 

LRC1

‘F’

‘E’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LRC0 check

‘A’

‘D’

 

 

‘0’

 

 

LRC0

‘D’

‘3’

 

LRC0

‘D’

‘3’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

End word 1

CR

CR

 

LRC1 check

‘0’

‘E’

 

End word 1

CR

CR

 

End word 1

CR

CR

End word 0

LF

LF

 

LRC0 check

‘3’

‘4’

 

End word 0

LF

LF

 

End word 0

LF

LF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

End word 1

CR

CR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

End word 0

LF

LF

 

 

 

 

 

 

 

 

yLRC Check

LRC check sums up from “machine address” to “data content”, e.g. 01H + 03H + 10H+ 00H + 00H + 02H = 16H. Obtain 2’s complement EA.

y RTU Mode

Read Command

 

 

Read Response Message

 

 

Write Command

 

 

Write Response Message

 

Machine address

01H

01H

 

Machine address

01H

01H

 

Machine address

01H

01H

 

Machine address

01H

 

01H

Command

03H

01H

 

Command

03H

01H

 

Command

06H

05H

 

Command

06H

 

05H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Read start address

10H

08H

 

Length of response

04H

02H

 

Write data address

10H

08H

 

Write data address

10H

 

08H

 

 

 

 

 

 

 

 

 

 

of data

00H

10H

 

data (byte)

 

 

 

 

01H

10H

 

 

01H

 

10H

 

 

 

 

 

 

 

 

 

 

Read length of data

00H

00H

 

Data content 1

01H

17H

 

Write data content

03H

FFH

 

Write data content

03H

 

FFH

(bit/word)

02H

09H

 

F4H

01H

 

20H

00H

 

20H

 

00H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRC low byte

C0H

BBH

 

Data content 2

03H

 

 

CRC low byte

DDH

8FH

 

CRC low byte

DDH

 

8FH

CRC high byte

CBH

A9H

 

20H

 

 

CRC high byte

E2H

9FH

 

CRC high byte

E2H

 

9FH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRC low byte

BBH

77H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRC high byte

15H

88H

 

 

 

 

 

 

 

 

 

yCRC Program Example

unsigned int reg_crc = 0xffff; i = 0; while (length--)

{

reg_crc ^= RTUData[i];

 

i ++;

 

for (j = 0; j < 8; j++)

 

{

 

if (reg_crc & 0x01)

reg_crc = (reg_crc >> 1) ^ 0xA001;

else

reg_crc = reg_crc >> 1;

}

 

}

 

return(reg_crc);

 

Installation

How to connect maximum 8 DTC1000/2000 controllers by using DIN rail.

How to Set Up Current Input

For general inputFor current input (4 ~ 20mA, 0 ~ 20mA)

JU MPER

J UMPER

JP1

PIN HEADER

JP1

 

 

 

PIN HEADER

DEFAULT SETTING

 

 

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation

Page 2
Image 2
Delta Electronics DTC2000 Series LED Display, Password Function, Synchronous Communication Protocol & Auto ID Setup, i ++