3
PG-02 Terminal Descriptions
Terminals
Terminal Symbols | Descriptions | |||||
|
|
|
|
|
| |
| VP | Power source of | ||||
| Output Voltage: (+12VDC ±5% 200mA) or (+5VDC ±2% 400mA) | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
| DCM | Power source (VP) and input signal (A, B) common | ||||
|
|
|
|
|
| |
|
|
|
|
| Input signal from Pulse Generator. Input type is selected by FSW2. | |
|
|
|
|
| ||
|
|
|
|
| Maximum 500KP/Sec | |
|
|
|
|
|
| |
A/O, B/O | ||||||
Maximum DC24V 300mA | ||||||
|
|
|
|
| ||
|
|
| ||||
| COM | |||||
|
|
|
|
|
|
Wiring Notes
The control, power supply and motor leads must be laid separately. They must not be fed through the same cable conduit / trunking.
1.Please use a shield cable to prevent interference. Do not run control wire parallel to any high voltage AC power line (220 V and up).
2.Connect shielded wire to E only.
3.Recommended wire size 0.21 to 0.81mm2 (AWG24 to AWG18).
4.Wire length:
Types of Pulse | Maximum Wire Length | Wire Gauge | |
Generators | |||
|
| ||
Output Voltage | 50m |
| |
|
|
| |
Open Collector | 50m | 1.25mm2 (AWG16) or above | |
|
| ||
Line Driver | 300m | ||
| |||
|
|
| |
Complementary | 70m |
| |
|
|
|