Image 25

TECHNICAL SPECIFICATIONS

ITEM/FEATURES

Office Pro 18

Rating Conditions

 

dry bulb

95º F (35º C)

wet bulb

83º F (28.2º C)

humidity

(60%)

 

 

Specifications

 

power frequency

60Hz

line voltage

single phase 115 V

power consumption

1.7 KW

current consumption

15.6 Amps

power factor

95%

starting current

54A

power wiring

12 (3-core) AWG

 

 

Cooling Unit

 

cooling capability

4,230 Kcal/hr

 

16,800 BTU/hr

cooling system

direct expansion

Blower

 

type of fan

centrifugal fan

air volume: Evaporator (High speed)

540 ft 3/min (913 m3/h)

Condenser (High speed)

770 ft 3/min (1301 m3/h)

motor output (High)

0.24 KW

(Low)

0.19 KW

Compressor

 

type

rotary

output

0.95 Kw

refrigerant type

R-22

refrigerant capacity

1.54 lbs (0.70 kg)

 

 

Safety Devices

 

compressor overload protector

included

fan motor protector

included

anti-freezing thermistor

included

full drain tank switch

included

automatic restart (power interruption)

included

compressor time delay program

included

Dimensions & Weight

 

W x D x H (in)

21" x 27" x 44"

W x D x H (mm)

538 x 696 x 1118

weight (lbs/kg)

210 / 95

 

 

Operating Conditions

 

inlet air (relative humidity)

95º F (35º C), 60%

 

65º F (18,3º C), 60%

 

 

Control Device

 

temperature control

included

programmable timer

included

two speed fan

included

 

 

19