HOSE INSTALLATION
Note: The OP60 is equipped with a 20 foot (6 m) hose.
Connect the 20 foot (6 m) hose to the drain outlet spout and feed it through the grommet on the right hand side of the unit.
Note: Do not use more than 18 feet (5.5 m) of drain hose vertically. This is the maximum head (lift) of the Condensate Pump.
When securing the drain hose to the highest vertical position (no more than 18 feet (5.5m)) and running the hose to the drain, run the drain hose on a downward slope at a rate minimum of 1/4 inch (6.25 mm) per foot for proper drainage.
DRAIN STEM
DRAIN HOSE
DRAIN HOSE
DRAIN HOLE
1/4" (6.25 mm)
TAPER PER FOOT
18' (5.5 m) MAX
CONDENSATE
PUMP
GROMMET