AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation

Determining Fresh-Air Flow for Fireplace Location

AIR FOR COMBUSTION AND VENTILATION

WARNING: This fireplace shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate com- bustion and ventilation air. Read the following in- structions to insure proper fresh air for this and other fuel-burning appliances in your home.

Today’s homes are built more energy efficient than ever. New mate- rials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable win- dows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of these three criteria, you must provide additional fresh air. See Ventilation Air From Outdoors, page 8.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Fireplace Location, below.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 16 ft. (length) x 14 ft. (width) x 8 ft. (ceiling height) = 1792 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 1792 cu. ft. (volume of space) x 20 = 35,840 (maximum Btu/Hr the space can support)

For..com

107032-01H

Page 6
Image 6
Desa and EFS26NR, EFS10TP, EFS10TN installation manual AIR for Combustion and Ventilation, Providing Adequate Ventilation

EFS10TP, EFS10TN, and EFS26NR specifications

Desa is a recognized leader in the innovation and manufacture of advanced heating solutions designed to deliver optimal performance and efficiency. Among their most notable offerings are the EFS26NR, EFS10TP, and EFS10TN models, each engineered with unique features and technologies to meet diverse heating needs.

The EFS26NR is a notable model known for its large heating capacity and effectiveness in maintaining consistent warmth in larger spaces. With a robust output, this unit can efficiently heat areas up to 1,800 square feet, making it suitable for homes or commercial settings. One of the primary characteristics of the EFS26NR is its advanced heating technology, which includes a high-efficiency burner that maximizes fuel usage, reducing operational costs. Additionally, it features a built-in thermostat, providing automated temperature adjustments for enhanced comfort.

On the other hand, the EFS10TP is designed for versatility and practicality. This model is ideal for smaller rooms or as a supplementary heating option. The EFS10TP offers users the convenience of a portable heater equipped with wheels, allowing for easy mobility. This model is equipped with user-friendly controls and a safety shut-off feature, ensuring peace of mind while in use. The EFS10TP utilizes a compact design without sacrificing performance, allowing it to fit seamlessly into various settings.

Similar in size, the EFS10TN focuses on energy efficiency as its main selling point. This model uses a unique infrared heating technology that allows for more direct heating of objects and people rather than warming the air, resulting in lower energy consumption. The EFS10TN is perfect for those looking to reduce their carbon footprint while still achieving a warm, inviting environment. Enhanced safety features such as tip-over protection and overheat shut-off further ensure its suitability for use in homes with children or pets.

Overall, the Desa heating solutions—EFS26NR, EFS10TP, and EFS10TN—each provide distinct advantages tailored to specific heating requirements. With a commitment to innovation, safety, and efficiency, these models are exemplary choices for those seeking dependable and effective heating options. Whether for large areas or cozy spaces, Desa ensures that there is a suitable solution for every heating need.