VENTILATION
!WARNING
Never use heater without properly installed vent pipe and regulator. You must vent heater to the outdoors. This as- sures proper combustion and avoids air contamination in the room.
A standard 4 inch (10.16 cm) draft regulator is required only if total vertical and horizontal length of the vent pipe exceeds 20 feet (6.1 meters). Regulator, vent pipe, and fi ttings are not supplied with the heater. Purchase these items at a local hardware store.
Standard 4 inch (10.16 cm) draft regulator (required if vent pipe ex- ceeds 20 feet [6.1 meters] in length).
30" (76.2 cm) Mini- mum
If horizontal run is needed, use at least 1 foot (30.48 cm) rise for each 10 feet (3.05 meters) of run.
OPERATION
125 VENTILATION | PFA/PV 023 |
Figure 4 - Ventilation Requirements
!WARNING
Review and understand the warnings in the Safety Informa- tion Section. They are needed to safely operate this heater. Follow all local codes when using this heater.
To Start Heater
1.Follow all ventilation and safety information.
2.Fill fuel tank with kerosene or No. 1 fuel oil.
3.Attach fuel cap.
4.Plug power cord into standard 230 volt/50 hertz, grounded (earthed) outlet. Use an extension cord if needed. Use only a
Extension Cord Wire Size Requirements
Up to 100 feet (30.5 meters) long, use 16 AWG (1.0 mm2 ) conductor
101 to 200 feet (30.6 to 61 meters) long, use 14 AWG (1.5 mm2 ) conductor
Heater will start when power cord is plugged into outlet. If not, push in flame- out control reset button (see Figure 5).
Control
Reset Button
(Fan Guard
Removed)
Figure 5 - Flame-Out Control Reset Button
Continued | 7 |
|
|