Desa CGD3018P Installing, Continued, raise the mantel to an acceptable height, OR

Models: CGD3018P

1 32
Download 32 pages 21.01 Kb
Page 12
Image 12
•raise the mantel to an acceptable height, OR

INSTALLING

Mantel Shelf

Continued

 

12"

 

 

 

10"

 

 

 

8"

 

 

 

6"

 

 

 

2 1/2"

 

 

Minimum Non-

 

 

 

Combustible

 

 

 

Material

8"

12"

15"

 

 

Min.

 

 

 

Hood

Distances to

 

(GA6050, GA6052)

 

Underside of

 

 

 

 

Mantel

18"

Underside of

Mantel Shelf

All minimum distances are in inches

Log Set

20"Manual background 18", 24", 30" Models

Top of Fireplace Opening

Figure 7 - Minimum Mantel Clearances When Using Hood

If your installation does not meet the above minimum clearances, you must:

operate the logs only with the flue damper open, OR

raise the mantel to an acceptable height, OR

remove the mantel.

Floor Clearances

A.If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).

14"

Combustible Material

12

Min.

Manual backgroundNon-Combustible Material

Figure 8 - Minimum Fireplace Clearances If Installed at Floor Level

B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combustible flooring (see Figure 9).

Hearth

Combustible Material

5"

Min.

Figure 9 - Minimum Fireplace Clearances Above Combustible Flooring