AIR FOR COMBUSTION AND VENTILATION

WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven- tilation air. Read the following in- structions to insure proper fresh air for this and other fuel-burning appliances in your home.

Today’s homes are built more energy effi- cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com- bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide ad- equate fresh air for these appliances. This will insure proper venting of vented fuel- burning appliances.

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code. NFPA 54/ANS Z223.1, Sec- tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 4 through 6 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and win- dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is de- fined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a con- tinuous water vapor retarder with a rating of one perm (6x10-11kg per pa-sec-m2) or less with open- ings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, be- tween sole plates and floors, be- tween wall-ceiling joints, be- tween wall panels, at penetra- tions for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide ad- ditional fresh air. See Ventilation Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to De- termining Fresh-Air Flow For Heater Location, page 5.

Confined and Unconfined Space

The National Fuel Gas Code ANS Z223.1 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggre- gate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are con- sidered a part of the unconfined space.

This heater shall not be installed in a con- fined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.

*Adjoining rooms are communicating only if there are doorless passageways or ventila- tion grills between them.

4

104276

Page 4
Image 4
Desa CGN10RLA AIR for Combustion and Ventilation, Providing Adequate Ventilation, Unusually Tight Construction

CGN10RLA specifications

Desa CGN10RLA is a cutting-edge generator that exemplifies modern engineering and design, making it a popular choice among residential and commercial users alike. This generator stands out for its reliability and efficiency, characteristics that are essential for those who require a consistent power supply in various situations, from home use during outages to outdoor recreational activities.

One of the main features of the Desa CGN10RLA is its robust engine, which delivers a powerful output of up to 10,000 watts. This high capacity makes it suitable for running heavy-duty appliances and tools. Whether you need to power your air conditioning unit during a summer heatwave or run multiple devices on a construction site, this generator has the power to meet your needs.

The CGN10RLA also boasts impressive fuel efficiency. Its advanced fuel management system allows for longer run times on a single tank, which is a significant advantage for users looking to minimize interruptions and maximize productivity. This generator is designed to accommodate a variety of fuel types, providing flexibility and convenience for users.

Equipped with a state-of-the-art inverter technology, the Desa CGN10RLA guarantees stable power output with less than 3% total harmonic distortion. This feature is particularly important for sensitive electronic devices, ensuring that they are safeguarded against power surges that could lead to damage. Thus, users can confidently run their office equipment, computers, and other delicate electronics without concern.

Portability is another highlight of the CGN10RLA. The generator is designed with integrated wheels and a folding handle, making it easy to transport. Its compact size means it can fit into tight storage spaces, while still providing ample power when needed.

In terms of safety, the Desa CGN10RLA incorporates several protective features such as low oil shutdown and overload protection, ensuring the safe operation of the unit. This generator is also equipped with a user-friendly control panel, allowing for straightforward operation and accessibility.

Overall, the Desa CGN10RLA is a versatile generator that combines power, efficiency, and convenience. Whether for home use, travel, or professional projects, its advanced technology and user-centric design make it an excellent choice for anyone in need of reliable power.