6

AIR FOR COMBUSTION AND VENTILATION

Ventilation Air

INSTALLATION

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code ANSI Z223.1/ NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

INSTALLATION

NOTICE: This heater is intended for use as supple- mental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

WARNING: A qualified service person must in-

Room,

Or

Option 2

stall heater. Follow all local codes.

Option 1

Remove

Door into Adjoining Room, Option 3

12"

Figure 2 - Ventilation Air from Inside Building

NOTICE: State or local codes may only allow opera- tion of this appliance in a vented configuration. Check your state or local codes.

WARNING: Before installing in a solid fuel burn- ing fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue may create and distribute soot within the house. Inspect chimney flue and firebox for damage. If damaged, repair flue before operating heater.

For..com

107068-01H

Page 6
Image 6
Desa SGS3124N, SGS3124P Installation, Ventilation AIR, Ventilation Air From Inside Building, Ventilation Air From Outdoors

SGS3124N, SGS3124P, CLD3018NT, CLD3018PT specifications

The Desa CLD3018PT, CLD3018NT, SGS3124N, and SGS3124P are innovative heating solutions designed for both practicality and efficiency. These products cater to the distinct needs of consumers looking for reliable heating options for their living spaces, workshops, or garages.

The CLD3018PT and CLD3018NT models stand out due to their portability and lightweight design. They feature advanced heating technology that ensures quick and consistent warmth, making them an ideal choice for temporary or supplemental heating. The CLD3018PT is equipped with a propane tank connection for efficient energy use, while the CLD3018NT integrates natural gas functionality, providing versatility in fuel source depending on consumer needs. Both models utilize an advanced safety system that includes automatic shut-off mechanisms and tip-over protection, making them safe for indoor and outdoor use.

On the other hand, the SGS3124N and SGS3124P models are designed for more permanent heating solutions. The SGS3124N operates on natural gas, making it an excellent choice for homeowners looking to minimize their carbon footprint. The SGS3124P provides a propane option, catering to users who may not have a natural gas line available. Both models are built with durable materials that ensure longevity and performance, even under heavy use. Their efficient heating technologies are capable of warming larger spaces quickly, making them suitable for workshops and other substantial areas.

In terms of features, all four models incorporate user-friendly controls that allow for easy temperature adjustment and settings management. The presence of safety features in these products reinforces their reliability, accommodating users' needs without compromising on safety.

Overall, the Desa CLD3018PT, CLD3018NT, SGS3124N, and SGS3124P represent a fusion of innovation, safety, and efficiency in the heating market. These models cater to a diverse range of heating needs, appealing to various customers from casual users who require portability to homeowners seeking a permanent heating solution. By emphasizing advanced technology and user safety, Desa continues to uphold its reputation for providing high-quality heating appliances.