Desa SGS3124N Installation, Ventilation Air, Air For Combustion And Ventilation, Continued

Models: SGS3124N SGS3124P CLD3018NT CLD3018PT

1 36
Download 36 pages 30.48 Kb
Page 6
Image 6
INSTALLATION

6

AIR FOR COMBUSTION AND VENTILATION

Ventilation Air

INSTALLATION

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code ANSI Z223.1/ NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

INSTALLATION

NOTICE: This heater is intended for use as supple- mental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

VENTILATION AIR WARNING: A qualified service person must in-

Room,

Or

Option 2

stall heater. Follow all local codes.

Option 1

Remove

Door into Adjoining Room, Option Figure 3 - Ventilation Air from Outdoors 3

12"

Figure 2 - Ventilation Air from Inside Building

NOTICE: State or local codes may only allow opera- tion of this appliance in a vented configuration. Check your state or local codes.

Figure 2 - Ventilation Air from Inside Building WARNING: Before installing in a solid fuel burn- ing fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue may create and distribute soot within the house. Inspect chimney flue and firebox for damage. If damaged, repair flue before operating heater.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundForManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background.Manual backgroundManual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual background

107068-01H

Page 6
Image 6
Desa SGS3124N, CLD3018PT Installation, Air For Combustion And Ventilation, Continued, Ventilation Air from Outdoors