OWNER’S MANUAL
INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible ma- terial clearances, you must also meet required clearances between fireplace open- ings and mantel shelf on each side of the fireplace. If you do not meet the clearances listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel shelf and top of fireplace opening, a
10"
8"
6"
2 1/2"
Minimum Non- |
|
| (A) | |
| ||||
Combustible | ||||
| ||||
Material |
| |||
|
|
| 12" | |
|
|
|
|
Mantel Shelf
18" |
| 20" | 22" |
| |||
|
|
|
|
Underside of
Mantel Shelf
All minimum distances are in inches
24"
Top of Fireplace
Opening
hood is not required (see Figure 6).
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clear-
Minimum Non- | Distances to |
Combustible | Underside of |
Material Height | Mantel |
Figure 6 - Minimum Mantel Clearances Without Using Hood
Mantel Shelf
ances shown in Figure 7 when using hood.
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:
•operate the logs only with the flue damper open
•raise the mantel to an accept- able height
•remove the mantel
FLOOR CLEARANCES
A. | If installing appliance on the floor level, |
| you must maintain the minimum dis- |
| tance of 14" to combustibles (see Fig- |
| ure 8). |
B. | If combustible materials are less than |
12"
10"
8"
6"
2 1/2"
Minimum Non-
Combustible
Material
8"
Min.
Hood
(HDABK, HDABR)
12" | 15" |
|
|
Distances to Underside of Mantel
18"
Underside of
Mantel Shelf
All minimum distances are in inches
20" Log Sets
All Models
Top of Fireplace Opening
14" to the fireplace, you must install |
appliance at least 5" above the combus- |
tible flooring (see Figure 9). |
Figure 7 - Minimum Mantel Clearances When Using Hood
Combustible | Hearth | Combustible | |
14" Material | |||
Min. |
| Material | |
|
| 5" | |
|
| Min. | |
Figure 9 - Minimum Fireplace Clearances | |||
Figure 8 - Minimum Fireplace Clearances | |||
Above Combustible Flooring | |||
If Installed at Floor Level | |||
| Continued | ||
|
|
105223 | 9 |