AIR FOR COMBUSTION AND VENTILATION

Continued

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_ ________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20

= 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

___________ Btu/Hr

Gas water heater*

___________ Btu/Hr

Gas furnace

___________ Btu/Hr

Vented gas heater

___________ Btu/Hr

Gas fireplace logs

___________ Btu/Hr

Other gas appliances* +__________ Btu/Hr

Total

=__________ Btu/Hr

*Do not include direct-vent gas appliances.

Direct-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

40,000

 

Gas water heater

 

 

___________ Btu/Hr

Vent-free fireplace

+_

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/

Hr used.

_ _______ Btu/Hr (maximum the space can support)

_ _______ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of

Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can sup- port. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms.

See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated does not meet the required volume for indoor combustion air, combustion and ventilation air shall be provided by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54, the International Fuel Gas Code, or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

 

 

12"

Ventilation

 

Ventilation Grills

Grills

 

Into Adjoining

Or

Into Adjoining Room,

Room,

Option 2

Remove

Option 1

 

Door into

 

 

 

 

Adjoining

 

 

Room,

 

 

Option

 

 

3

 

12"

Figure 3 - Ventilation Air from Inside

Building

113109-01G

www.desatech.com

7